Input data (0x60A0)

For all analog input modules: AI_1xC (0x382199), AI_1xV (0x302199)

Index 60A0 SlotGroup 4 (Slot 11) AI Inputs 1

Index (hex)

Name

Meaning

Data type

Flags

Default

60A0:0

SlotGroup 4
(Slot 11)
AI Inputs 1

Maximum subindex

UINT8

RO

0x11 (17dec)

60A0:01

Underrange

Value below measuring range

BOOLEAN

RO

0x00 (0dec)

60A0:02

Overrange

Measuring range exceeded

BOOLEAN

RO

0x00 (0dec)

60A0:03

Limit 1

Limit value monitoring Limit 1

0: not active
1: value is less than limit value 1
2: value is greater than limit value 1
3: value is equal to limit value 1

BIT2

RO

0x00 (0dec)

60A0:05

Limit 2

Limit value monitoring Limit 2

0: not active
1: value is less than limit value 2
2: value is greater than limit value 2
3: value is equal to limit value 2

BIT2

RO

0x00 (0dec)

60A0:07

Error

The error bit is set if the data is invalid (overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

60A0:11

Value

Analog input date

INT16

RO

0x0000 (0dec)