1000 - 10F8 (Device)
Index 1000 Device type
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 1000:0 | Device type | Device type of the EtherCAT slave: the Lo-Word contains the used CoE profile (5001). The Hi-Word contains the module profile according to the modular device profile. | UINT32 | RO | 0x00001389 (5001dec) | 
Index 1008 Device name
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 1008:0 | Device name | Device name of the EtherCAT slave | STRING | RO | EP8601-0022 | 
Index 1009 Hardware version
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 1009:0 | Hardware version | Hardware version of the EtherCAT slave | STRING | RO | 09 | 
Index 100A Software version
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 100A:0 | Software version | Firmware version of the EtherCAT slave | STRING | RO | 10 | 
Index 100B Bootloader version
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 100B:0 | Bootloader version | Bootloader version | STRING | RO | 
 | 
Index 1011 Restore default parameters
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 1011:0 | Restore default parameters | Restore default parameters | UINT8 | RO | 0x01 (1dec) | 
| 1011:01 | SubIndex 001 | If this object is set to "0x64616F6C" in the Set Value dialog, all backup objects are reset to their delivery state. | UINT32 | RW | 0x00000000 (0dec) | 
Index 1018 Identity
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 1018:0 | Identity | Information for identifying the slave | UINT8 | RO | 0x04 (4dec) | 
| 1018:01 | Vendor ID | Vendor ID of the EtherCAT slave | UINT32 | RO | 0x00000002 (2dec) | 
| 1018:02 | Product code | Product code of the EtherCAT slave | UINT32 | RO | 0x21994052 (563691602dec) | 
| 1018:03 | Revision | Revision number of the EtherCAT slave; the Low Word (bit 0-15) indicates the special terminal number, the High Word (bit 16-31) refers to the device description | UINT32 | RO | 0x00000000 (0dec) | 
| 1018:04 | Serial number | Serial number of the EtherCAT slave; the Low Byte (bit 0-7) of the Low Word contains the year of production, the High Byte (bit 8-15) of the Low Word contains the week of production, the High Word (bit 16-31) is 0 | UINT32 | RO | 0x00000000 (0dec) | 
Index 10E2 Manufacturer-specific Identification Code
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 10E2:0 | Manufacturer-specific Identification Code | Manufacturer specific identification code | UINT8 | RO | 0x01 (1dec) | 
| 10E2:01 | SubIndex 001 | 
 | STRING | RO | 
 | 
Index 10F0 Backup parameter handling
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 10F0:0 | Backup parameter handling | Information for standardized loading and saving of backup entries | UINT8 | RO | 0x01 (1dec) | 
| 10F0:01 | Checksum | Checksum across all backup entries of the EtherCAT slave | UINT32 | RO | 0x00000000 (0dec) | 
Index 10F3 Diagnosis History
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 10F3:0 | Diagnosis History | Maximum subindex | UINT8 | RO | 0x37 (55dec) | 
| 10F3:01 | Maximum Messages | Maximum number of stored messages | UINT8 | RO | 0x00 (0dec) | 
| 10F3:02 | Newest Messages | Subindex of the newest message | UINT8 | RO | 0x00 (0dec) | 
| 10F3:03 | Newest Acknowledged Messages | Subindex of the last acknowledged message | UINT8 | RW | 0x00 (0dec) | 
| 10F3:04 | New Messages Available | Indicates that a new message is available | BOOLEAN | RO | 0x00 (0dec) | 
| 10F3:05 | Flags | not used | UINT16 | RW | 0x0000 (0dec) | 
| 10F3:06 | Diagnosis Message 001 | Message 1 | OCTET-STRING[20] | RO | {0} | 
| … | … | … | … | … | … | 
| 10F3:37 | Diagnosis Message 050 | Message 16 | OCTET-STRING[20] | RO | {0} | 
Index 10F8 Actual Time Stamp
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 10F8:0 | Actual Time Stamp | Current time stamp | UINT64 | RO | 
 |