Presentation
The measured value is output ex factory in two's complement presentation (signed integer).
The presentation of the measured value can be changed via index 0x80B0:02 "Presentation".
Value  | Data format  | Description  | 
|---|---|---|
0  | "Signed presentation"  | Signed integer presentation Maximum presentation range for 16 bit = -32768... +32767dec  | 
1  | "Unsigned presentation"  | Unsigned integer presentation Maximum presentation range for 16 bit = 0... +32767dec  | 
2  | "Absolute MSB sign"  | Absolute value MSB sign - presentation Maximum presentation range for 16 bit = -32767... +32767dec  | 
3  | "Absolute value"  | Absolute value - presentation  | 
Input signal for the measuring ranges  | Value (with Extended Range)  | Value (with Legacy Range)  | ||||||
|---|---|---|---|---|---|---|---|---|
4 … 20 mA  | 0 … 20 mA  | ±10 V  | Signed  | Unsigned  | Absolute MSB sign  | Signed  | Unsigned  | Absolute MSB sign  | 
21.474 mA  | 21.474 mA  | 10.737 V*  | 0x7FFF  | 0x7FFF  | 0x7FFF  | 
  | 
  | 
  | 
20 mA  | 20 mA  | 10 V*  | 0x7736  | 0x7736  | 0x7736  | 0x7FFF  | 0x7FFF  | 0x7FFF  | 
12 mA  | 10 mA  | 5 V*  | 0x3B9A  | 0x3B9A  | 0x3B9A  | 0x3FFF  | 0x3FFF  | 0x3FFF  | 
  | 
  | 
  | 0x0001  | 0x0001  | 0x0001  | 0x0001  | 0x0001  | 0x0001  | 
4 mA  | 0 mA  | 0 V*  | 0x0000  | 0x0000  | 0x0000  | 0x0000  | 0x0000  | 0x0000  | 
  | 
  | 
  | 0xFFFF  | 0x0001  | 0x8001  | 0xFFFF  | 0x0001  | 0x8001  | 
3.8 mA  | 
  | 
  | 0xFE83  | 0x017D  | 0x817D  | 
  | 
  | 
  | 
0 mA  | 
  | 
  | 0xE233  | 0x1DCD  | 0x9DCD  | 
  | 
  | 
  | 
  | 
  | -5 V  | 0xC466  | 0x3B9A  | 0xBB9A  | 0xC001  | 0x3FFF  | 0xBFFF  | 
  | 
  | -10 V  | 0x88CA  | 0x7736  | 0xF736  | 0x8000  | 0x7FFF  | 0xFFFF  | 
-21.474 mA  | 
  | -10.737 V*  | 0x8000  | 0x7FFF  | 0xFFFF  | 
  | 
  | 
  | 
*) Values also apply to the unipolar measuring range 0 ... 10 V  | ||||||||