Current output "AO_1xC" output ranges

1. Set the output range via index 0x80BD:11 "Output type".
(see table "Output ranges and scaling type")
2. Select the scaling type via index 0x80BD:12 "Scaler":

Scaling type

0x80BD:12
"Scaler"

Name

Resolution 1 LSB

Meaning

0x0000 (0dec)

Extended Range

Current output "AO_1xC" output ranges 1:

This type of scaling allows the nominal output range to be exceeded or undershot by approx. 7 %. The technically usable range is -107 % to +107 % of the respective full scale value. For the "Extended Range", the PDO value ±30518 (0x7736) is defined as 100 % for 16 bits.

0x0003 (3dec)

Legacy Range

Current output "AO_1xC" output ranges 2:

This scaling type shows the range from -100 % to +100 %.

  • +100 % corresponds to +32767
  • -100 % corresponds to -32768

Output ranges and scaling type

0x80BD:11
"Output type"

Current output ranges

Extended Range

0x80BD:12 "Scaler" = 0dec

Legacy Range

0x80BD:12 "Scaler" = 3dec

Full scale value (FSV)

0x0012 (18dec)

0 … +21.474 mA

0 … +20 mA

20 mA

0x0013 (19dec)

0 … +21.474 mA

4 … +20 mA

20 mA

The following status bits report that the output range has been exceeded:

A complete description of these status bits can be found in the chapter Output range monitoring.

Graphical representation of the output ranges

Current output "AO_1xC" output ranges 3: