Voltage measurement "AI_1xV" measuring ranges
- 1. Set the measuring range via index 0x80AD:11 “Input type”
(see table “Measuring ranges and scaling type”). - 2. Select the scaling type via index 0x80AD:12 “Scaler”:
Scaling type
0x80AD:12 | Name | Resolution 1 LSB | Meaning |
---|---|---|---|
0x0000 (0dec) (pre-set) | Extended Range | This type of scaling allows the nominal measuring range to be exceeded or undershot by approx. 7 %.
| |
0x0003 (3dec) | Legacy Range | This scaling type shows the range from -100 % to +100 %.
Nominal measuring range = Technical measuring range |
Measuring ranges and scaling type
0x80AD:11 | Voltage measuring ranges | ||
---|---|---|---|
Extended Range 0x80AD:12 "Scaler" = 0x0000 (0dec) | Legacy Range 0x80AD:12 "Scaler" = 0x0003 (3dec) | Full scale value (FSV) | |
0x0002 (2dec) | -10.737 … +10.737 V | -10 … +10 V | 10 V |
0x000E (14dec) | 0 … +10.737 V | 0 … +10 V | 10 V |
The following status bits indicate that the measuring range has been exceeded:
- Underrange / Overrange: the corresponding bits are set if the measured value is outside the nominal measuring range.
- Range Error: The error thresholds for the error bit and the error LED can be set in "Extended Range" mode via parameter 0x80AD:17 "Low Range Error" and parameter 0x80AD:18 "High Range Error". The "Extended Range" limit values are pre-set.
A complete description of these status bits can be found in the chapter Measuring range monitoring.
Schematic diagram of the measuring ranges
