Analog current/voltage input, AI_1xC, AI_1xV (0x382199, 0x302199)
Overview 0x1AA0 for analog input (SlotGroup 4)
Index (hex) | Index name for ModuleGroups (ModuleIdent): | |
|---|---|---|
AI_1xC (0x382199) | AI_1xV (0x302199) | |
1AA0:0 | AI_1xC TxPDO‑Map SlotGroup 4 (Slot 11) Inputs 1 | AI_1xV TxPDO‑Map SlotGroup 4 (Slot 11) Inputs 1 |
Index 1AA0 AI_1xC/1xV TxPDO-Map SlotGroup 4 (Slot 11) Inputs 1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1AA0:0 | AI_1xC/1xV TxPDO-Map SlotGroup 4 | PDO Mapping TxPDO 9 | UINT8 | RO | 0x07 (7dec) |
1AA0:01 | SubIndex 001 | 1. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x01 (Underrange)) | UINT32 | RO | 0x60A0:01, 1 |
1AA0:02 | SubIndex 002 | 2. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x02 (Overrange)) | UINT32 | RO | 0x60A0:02, 1 |
1AA0:03 | SubIndex 003 | 3. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x03 (Limit 1)) | UINT32 | RO | 0x60A0:03, 2 |
1AA0:04 | SubIndex 004 | 4. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x05 (Limit 2)) | UINT32 | RO | 0x60A0:05, 2 |
1AA0:05 | SubIndex 005 | 5. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x07 (Error)) | UINT32 | RO | 0x60A0:07, 1 |
1AA0:06 | SubIndex 006 | 6. PDO Mapping entry (9 bits align) | UINT32 | RO | 0x0000:00, 9 |
1AA0:07 | SubIndex 007 | 7. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x11 (Value)) | UINT32 | RO | 0x60A0:11, 1 |