Analog output

Analog output

Number

1

Output value

Optional current or voltage

Output signal ranges

Voltage output:

  • -10 … +10 V (default)
  • 0 … 10 V

Current output:

  • 0 … 20 mA
  • 4 … 20 mA

Resolution

12-bit (representation as 16 bit incl. sign)

Conversion time

approx. 500 µs

Load

Voltage output: > 5 kΩ (short-circuit proof)

Current output: < 350 Ω (short-circuit proof)

Output error

0.5 % of the full scale value of the signal range.

Largest short-term deviation during a specified electrical interference test

4 % of the full scale value of the signal range.