Diagnostics
The module offers various diagnostic options for users. These messages are divided into hardware warnings and hardware errors. The respective status words for the channels (except digital inputs and outputs) contain a bit for warnings and errors. The exact cause is analyzed via the diagnostic data (0xA050). Warnings are reset automatically. Errors may result in the output stage being switched off (PWMi) and have to be acknowledged in the control word (0x7050:07 Reset)
Error/warning for the PWM stage
Index (hex) | Warning | Meaning |
|---|---|---|
A050:02 | Overtemperature | from 100 °C |
A050:06 | Short circuit | An overcurrent/short circuit of more than 105% of the rated current has occurred for more than 200 ms |
Control voltage (Us) and peripheral voltage (Up) of the EP8309

DEV input process data | Meaning |
|---|---|
Undervoltage Us | Warning below 18 VDC |
Undervoltage Up | Warning below 18 VDC |