Parameterization

 

Parameterization 1:

Enter alternating current data as peak values

Parameterization 2:

All alternating current data must be entered as peak values.

  • If RMS values are specified in the motor data sheet, multiply them by √2 to convert them to a peak value.
    4 Arms must be converted to 5.657 Apeak, for example.

 

Motor parameters

Set the following parameters according to the specifications in the motor data sheet:

If the number of pole pairs of the motor is unknown, keep the parameter at the default value 1. The actual motor speed is then reduced by the factor "number of pole pairs" compared to the specified value.
After commissioning, you can determine the number of pole pairs experimentally, see chapter Determine number of pole pairs.

Further parameters

NC scaling factors