Configuration data (vendor-specific)
Index 801F DRV Vendor data
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
801F:0 |
DRV Vendor data |
Maximum subindex |
UINT8 |
RO |
0x14 (20dec) |
|
801F:11 |
Amplifier peak current |
Peak current of the amplifier (peak value) |
UINT32 |
RW |
0x00001F40 (8000dec) |
|
801F:12 |
Amplifier rated current |
Tated current of the amplifier (peak value) |
UINT32 |
RW |
0x00000FA0 (4000dec) |
|
801F:13 |
Amplifier thermal time constant |
Thermal time constant of the amplifier |
UINT16 |
RW |
0x0023 (35dec) |
|
801F:14 |
Amplifier overcurrent threshold |
Threshold value for short-circuit detection |
UINT32 |
RW |
0x00002EE0 (12000dec) |