Process data objects EP7041-0000

The EP7041-0000 device contains the process data for the encoder.

FB Inputs Channel 1

Process data objects EP7041-0000 1:

In BiSS® C mode

  • Warning
    Forwarded warning bit from the BiSS® C encoder telegram.
    For interpretation, see the encoder documentation.
  • Error
    Forwarded error bit from the BiSS® C encoder telegram.
    For interpretation, see the encoder documentation.
  • Ready
    The encoder signals that it is ready by a high level on the data line.
  • Diag
    Indicates that there are unread Diag Messages in Diag History.
  • TxPDO State
    Validity of the process data object "FB Inputs Channel 1".
    If this bit has the value 1, all current values of this process data object are invalid.
  • Input cycle counter
    A 2-bit counter that is incremented each time the process data object "FB Inputs Channel 1" is updated.
  • Position
    The current position value of the encoder.

 

In SSI mode

  • Warning
    No significance, as the parameter 8008:02 "Disable Status Bits" is automatically set to TRUE in SSI mode.
  • Error
    No significance, as parameter 8008:02 "Disable Status Bits" is automatically set to TRUE in SSI mode.
  • Ready
    The encoder signals that it is ready for operation with a high level on the data line.
  • Diag
    Indicates that a new Diag Message is available in the Diag History.
  • TxPDO State
    Validity of the process data object "FB Inputs Channel 1".
    If this bit has the value 1, all current values of this process data object are invalid.
  • Input cycle counter
    A 2-bit counter that is incremented each time the process data object "FB Inputs Channel 1" is updated.
  • Position
    The current position value of the encoder.

FB Outputs Channel 1

Process data objects EP7041-0000 2:

Set
Controls the "SET" digital output for zeroing the encoder position. "SET" is available at two connections:
Connection X01, pin 2
Connection X05, pin 7

Direction
Controls the digital output "DIR" to reverse the encoder counting direction. "DIR" is available at two connections:
Connection X02, pin 2
Connection X05, pin 8