EP6228-3142
Ports Class A
Pin | Function | Description | Core color 1) |
|---|---|---|---|
1 | L+ | Supply voltage (from US) | brown |
2 | DI | Digital input | white |
3 | L- | GND | blue |
4 | C/Q | IO-Link data cable | black |
5 | - | - | gray |
1) The core colors apply to M12 cables from Beckhoff. See chapter Accessories.
Ports Class B
Pin | Function | Description | Core color 1) |
|---|---|---|---|
1 | L+ | Sensor/logic supply (from US) | brown |
2 | P24 | Actuator supply (from UP) | white |
3 | L- | GND to L+ | blue |
4 | C/Q | IO-Link data cable | black |
5 | N24 | GND to P24 | gray |
1) The core colors apply to M12 cables from Beckhoff. See chapter Accessories.
Guidelines for connecting IO-Link cables
- Only connect or disconnect IO-Link cables when they are de-energized.
- When used in a hazardous EMC environment: ideally, use cable with plastic union nut.