Measuring range -20 … +20 mA
Technical data  | Measuring range  | 
|---|---|
Measuring range, nominal  | -20…+20 mA  | 
Measuring range, end value (full scale value)  | 20 mA  | 
Measuring range, technically usable  | -21.474…+21.474 mA, overcurrent-protected  | 
Fuse protection  | Internal overload limiting, continuous current resistant  | 
PDO resolution  | 16-bit, including sign  | 
PDO LSB (Extended Range)  | 655.35 nA  | 
PDO LSB (Legacy Range)  | 610.37 nA  |