Connectors
M12 sockets
|
Pin |
Inputs 1 and 2 |
Outputs 3 and 4 | ||
|---|---|---|---|---|
|
Symbol |
Description |
Symbol |
Description | |
|
1 |
UP |
Sensor supply + |
Out |
Analog output |
|
2 |
In + |
Analog input + |
UP |
Actuator supply + |
|
3 |
GNDP |
Sensor supply Ground |
Out GND |
Abalog ground |
|
4 |
In - |
Analog input - |
GNDP |
Actuator supply Ground |
|
5 |
Shield |
Shield | ||
Electrical isolation
The analog channels have a common analog ground potential. The analog ground potential is electrically isolated from the sensor supply and the actuator supply.
For certain applications, the electrical isolation must be removed by a jumper. Please refer to the Connection examples.