Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
Supply voltages | |
|---|---|
Connection | Input: M8 connector, 4-pin, A-coded Downstream connection: M8 socket, 4-pin, A-coded |
|
US nominal voltage |
24 VDC (-15 % / +20 %) |
US sum current: IS,sum | max. 4 A |
|
Current consumption from US |
120 mA |
UP nominal voltage | 0 … 30 VDC |
UP sum current: IP,sum | max. 4 A |
Current consumption from UP | = Output current from the auxiliary voltage outputs (pin 2 of the M12 sockets) |
Analog outputs | |
|---|---|
Number | 4 |
Connection | 4x M12 socket, 5-pin, A-coded |
Cable length | max. 30 m |
Signal type | Adjustable:
|
Load resistor / load | > 5 kΩ for voltage output < 500 Ω for current output |
Resolution | 16 bits (including sign) |
Output error | < 0.1% (ambient temperature 0 ... +55°C) Based on the signal range end value in each case. |
Largest short-term deviation during a specified electrical interference test | 0.5 % of the full scale value of the signal range |
Auxiliary voltage output | From the supply voltage UP, can be selected as desired up to 30 VDC. |
Housing data | |
|---|---|
Dimensions W x H x D | 30 mm x 126 mm x 26.5 mm (without connectors) |
Weight | approx. 165 g |
Installation position | variable |
|
Material |
PA6 (polyamide) |
Environmental conditions | |
|---|---|
Ambient temperature during operation | -25 … +60 °C |
Ambient temperature during storage | -40 … +85 °C |
Vibration resistance, shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection rating | IP65, IP66, IP67 (according to EN 60529) |
Approvals / markings | |
|---|---|
Approvals / markings *) | |
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
Test | Explanation |
|---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |