UL Requirements

The installation of the EtherCAT Box Modules certified by UL has to meet the following requirements.

Supply voltage

CAUTION

These UL requirements are valid for all supply voltages of all marked EtherCAT Box Modules.

For the compliance of the UL requirements the EtherCAT Box Modules should only be supplied

  • by a 24 V DC supply voltage, supplied by an isolating source and protected by means of a fuse (in accordance with UL248), rated maximum 4 Amp, or
  • by a 24 V DC power source, that has to satisfy NEC class 2.
    A NEC class 2 power supply shall not be connected in series or parallel with another (class 2) power source

CAUTION

To meet the UL requirements, the EtherCAT Box Modules must not be connected to unlimited power sources

Networks

CAUTION

To meet the UL requirements, EtherCAT Box Modules must not be connected to telecommunication networks.

Ambient temperature range

CAUTION

To meet the UL requirements, EtherCAT Box Modules have to be operated only at an ambient temperature range of -25 °C to +55 °C.

Marking for UL

All EtherCAT Box Modules certified by UL (Underwriters Laboratories) are marked with the following label.

UL Requirements 1:Fig.5: UL label