Self test
You can perform a self test to check the functionality of the accelerometer.
Notice | |
Incorrect measured values during the self test While the self test is running, the measured acceleration values do not correspond to the real acceleration.
|
Procedure
- 1. Give a positive edge to the variable "AI Acc Outputs" > "Start self test".
- The self test is started.
- 2. Wait until the variable "AI Acc X Inputs" > "Status" > "Self test status" takes the value 1.
- The self test is running.
- 3. Wait until the variable "AI Acc X Inputs" > "Status" > "Self test status" takes a value unequal to 1.
- The self test is completed.
- 4. Evaluate the result according to the table below.
- 5. Set the variable "AI Acc Outputs" > "Start self test" back to 0.
- The variable "AI Acc X Inputs" > "Status" > "Self test status" takes the value 0.
Possible values of "Self test status"
"Self test status" | Meaning |
---|---|
0 | Ready to start a self test. |
1 | Self test is running. |
2 | Self test completed. Sensor defective. |
3 | Self test completed. Sensor OK. |