Configuration objects
8pp0 PWM Settings Ch.n
- Channel 1: Index 8000
- Channel 2: Index 8010
- Channel 3: Index 8020
- Channel 4: Index 8030
Subindex (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
0 | PWM Settings Ch.n |
| USINT | RO | 0x22 (34dec) |
03 | Enable Dithering | Enables dithering. Dithering is a square wave signal that is modulated onto the current signal. See chapter Dithering. | BOOL | RW | 00 |
05 | Watchdog | Enables the watchdog. The watchdog sets the output to a defined value if EtherCAT communication is interrupted. See chapter Behavior on EtherCAT failure: watchdog. Possible values:
| USINT | RW | 0x0 (0dec) |
07 | Operation Mode | Operation mode. Possible values:
| USINT | RW | 0x0 (0dec) |
09 | Enable Feedforward | Enables the feedforward pre-control for the ohmic resistance of the load. Before enabling, set the parameter 8pp0:19 "Coil Resistance" correctly. | BOOL | RW | 00 |
0B | Offset | User calibration offset in [mA]. | INT | RW | 0x0 (0dec) |
0C | Gain | User calibration gain. | DINT | RW | 0x10000 (65536dec) |
0D | Default Output | Parameter for the watchdog. See chapter Behavior on EtherCAT failure: watchdog. | INT | RW | 0x0 (0dec) |
0E | Default Output Ramp | Parameter for the watchdog. See chapter Behavior on EtherCAT failure: watchdog. | UINT | RW | 0xFFFF (65535dec) |
10 | Max Current | Maximum output current. Specification in % of the parameter 8ppF:06 "Nominal Current" (2 A) | USINT | RW | 0x64 (100dec) |
12 | Kp Factor | Proportional component of the current controller. | UINT | RW | 0xFA (250dec) |
13 | Ki Factor | Integral component of the current controller. | UINT | RW | 0x4 (4dec) |
14 | Kd Factor | Differential component of the current controller. | UINT | RW | 0x0 (0dec) |
19 | Coil Resistance | The ohmic resistance of the connected inductance in [0.01 Ohm]. Must only be set when using feedforward pre-control (8pp0:09). | UINT | RW | 0xFA (250dec) |
1E | Dithering Frequency | Frequency of the dither in [Hz]. | UINT | RW | 0x64 (100dec) |
1F | Dithering Amplitude | Amplitude of the dither. Specified as a percentage of the maximum current configured via 8pp0:10. | USINT | RW | 0xA (10dec) |
Subindex (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
21 | Select Info Data 1 | Possible values:
| USINT | RW | 0x0 (0dec) |
22 | Select Info Data 2 | Possible values:
| USINT | RW | 0x1 (1dec) |