Basic configuration

Each channel can be configured individually. The parameters can be found in the following CoE objects:

Channel

CoE object

1

0x8000

2

0x8010

3

0x8020

4

0x8030

Take particular care when setting the following parameters before operation:

Maximum output current

CoE parameter 0x8pp0:10 "Max Current". Factory setting: 100 % corresponding to 2 A.

Set the parameter to a value less than or equal to the maximum permissible current IL,max of the connected load. The specification is in percent of the maximum possible output current of 2 A:

Basic configuration 1:

Example: For a load with a rated current of 0.5 A, the parameter "Max Current" must be set to 25 or lower. (corresponding to 25 % of 2 A)

Operation mode

CoE parameter 8pp0:07 "Operation Mode"

You can choose between the operation modes "Current Control" and "Voltage Control" for each channel. You can enable or disable the current controller by selecting the operation mode.

A graphical representation of the signal flows of the operation modes can be found in the chapter Signal flow.

In the factory setting, the operation mode "Current Control" is pre-set; the current controller is enabled. For inductive loads, "Current Control" is generally the correct operation mode.