Process image
Digital inputs
You can find the digital inputs at "Channel 1" to "Channel 8".
| Data types
|
Assigning process data to connections
Connection | Digital input |
|---|---|
X01, pin 2 | Channel 2 |
X01, pin 4 | Channel 1 |
X02, pin 2 | Channel 4 |
X02, pin 4 | Channel 3 |
X03, pin 2 | Channel 6 |
X03, pin 4 | Channel 5 |
X04, pin 2 | Channel 8 |
X04, pin 4 | Channel 7 |
Digital outputs
You can find the digital outputs at "Channel 9" to "Channel 16".
| Data types
|
Assigning process data to connections
Connection | Digital output |
|---|---|
X01, pin 2 | Channel 10 |
X01, pin 4 | Channel 9 |
X02, pin 2 | Channel 12 |
X02, pin 4 | Channel 11 |
X03, pin 2 | Channel 14 |
X03, pin 4 | Channel 13 |
X04, pin 2 | Channel 16 |
X04, pin 4 | Channel 15 |