Enabling individual process data objects
Proceed as follows to enable a process data object:
- 1. In Solution Explorer, select the relevant EtherCAT device and click on the Process Data tab. Using an EP1839-0042 as an example:

- In the PDO List field, you can see the available process data objects and their indices.

- 2. Select the category Outputs or Inputs in the Sync Manager field:
Process data objects with index 0x1A00...0x1AFF are "Inputs", index 0x1600...0x16FF are "Outputs".
- 3. Find the index of the desired process data object in the field PDO Assignment.

- 4. If necessary, disable a process data object that prevents the desired process data object from being enabled ("excluded by …"). Using 0x1A04 DIP Extended Diagnosis as an example:

- 5. Check the box next to the index of the desired process data object.