Connectors
| Note | |
| Risk of confusion: supply voltages and EtherCAT Defect possible through incorrect insertion. 
 | 
EtherCAT Box Modules have two green M8 sockets for the incoming and downstream EtherCAT connections.
Connection
| EtherCAT | M8  | Core colors | ||
|---|---|---|---|---|
| Signal | Contact | ZB9010, ZB9020, ZB9030, ZB9032, | ZB9031 and old versions of ZB9030, ZB9032, ZK1090-3xxx-xxxx | TIA-568B | 
| Tx + | 1 | yellow1) | orange/white | white/orange | 
| Tx - | 4 | orange1) | orange | orange | 
| Rx + | 2 | white1) | blue/white | white/green | 
| Rx - | 3 | blue1) | blue | green | 
| Shield | Housing | Shield | Shield | Shield | 
1) Core colors according to EN 61918
|  | Adaptation of core colors for cables ZB9030, ZB9032 and ZK1090-3xxxx-xxxx For standardization, the core colors of the ZB9030, ZB9032 and ZK1090-3xxx-xxxx cables have been changed to the EN61918 core colors: yellow, orange, white, blue. So there are different color codes in circulation. The electrical properties of the cables have been retained when the core colors were changed. |