Restore the delivery state
You can restore the delivery state of the backup objects as follows:
- 1. Ensure that TwinCAT is running in Config mode.
- 2. In CoE object 1011:0 "Restore default parameters" select parameter 1011:01 "Subindex 001". 
- 3. Double-click on "Subindex 001".
- The "Set Value Dialog" dialog box opens.
- 4. Enter the value 1684107116 in the "Dec" field.
 Alternatively: enter the value 0x64616F6C in the "Hex" field. 
- 5. Confirm with "OK".
- All backup objects are reset to the delivery state.
|  | Alternative restore value With some older modules the backup objects can be changed with an alternative restore value: An incorrect entry for the restore value has no effect. |