Objects for commissioning
Index 80n0 AO Settings Ch.1 - 4 (for 2 ≤ n ≤ 5)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80n0:0 |
AO Settings Ch.1 - 4 |
Maximum subindex |
UINT8 |
RO |
0x13 (19dec) |
|
80n0:01 |
Enable user scale |
FALSE |
BOOLEAN |
RW |
0x00 (0dec) |
|
80n0:02 |
Presentation |
0: |
BIT3 |
RW |
0x00 (0dec) |
|
80n0:05 |
Disable watchdog |
FALSE The watchdog is active. In the event of a failure of communication, the analog output value will be set to either the manufacturer's or the user's default value. The watchdog timer is deactivated. In the event of a failure of communication, the analog output value will not be set to either the manufacturer's or the user's default value. |
BOOLEAN |
RW |
0x00 (0dec) |
|
80n0:06 |
Enable user default output |
FALSE The manufacturer's value (0 V) will be output if the watchdog timer triggers If the watchdog timer triggers, the user-specific output value (object 0x80n0:13) will be output. |
BOOLEAN |
RW |
0x00 (0dec) |
|
80n0:11 |
Offset |
User scaling offset compensation |
INT16 |
RW |
0x0000 (0dec) |
|
80n0:12 |
Gain |
User scaling gain compensation: |
INT32 |
RW |
0x00010000 (65536dec) |
|
80n0:13 |
Default output |
Definition of the user-specific output value that is presented to the output if the watchdog timer for the cyclic communication triggers. |
INT16 |
RW |
0x0000 (0dec) |
Index 80nE AO Internal data Ch.1 - 4 (for 2 ≤ n ≤ 5)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80nE:0 |
AO Internal data Ch.1 - 4 |
Maximum subindex |
UINT8 |
RO |
0x01 (1dec) |
|
80nE:01 |
DAC raw value |
DAC raw value |
INT16 |
RO |
0x0000 (0dec) |
Index 80nF AO Vendor data Ch.1 - 4 (for 2 ≤ n ≤ 5)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80nF:0 |
AO Vendor data Ch.1 - 4 |
Maximum subindex |
UINT8 |
RO |
0x02 (2dec) |
|
80nF:01 |
Calibration offset |
Calibration offset |
INT16 |
RW |
0x0800 (2048dec) |
|
80nF:02 |
Calibration gain |
Calibration gain |
INT16 |
RW |
0x7D00 (32000dec) |
Index 8060 ENC Settings Ch.1 - 4 (for 6 ≤ n ≤ 9)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80n0:0 |
ENC Settings Ch.1 - 4 |
Maximum subindex |
UINT8 |
RO |
0x06 (6dec) |
|
80n0:02 |
Enable reset |
The counter is set to zero whenever a latch event occurs |
BOOLEAN |
RW |
0x00 (0dec) |
|
80n0:03 |
Enable up/down counter |
Enable up/down counter instead of the encoder |
BOOLEAN |
RW |
0x00 (0dec) |
|
80n0:04 |
Gate polarity |
0: Gate disabled |
BIT2 |
RW |
0x01 (1dec) |
|
80n0:06 |
Evaluation mode |
0: 1-fold (single evaluation) |
BIT2 |
RW |
0x03 (3dec) |
Index 80A0 PLS Settings
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80A0:0 |
PLS Settings |
Maximum subindex |
UINT8 |
RO |
0x12 (18dec) |
|
80A0:01 |
Encoder as PLS source |
0: Channel 1 is the source for PLS functions |
BIT2 |
RW |
0x00 (0dec) |
|
80A0:11 |
Output mask |
Determines which of the digital outputs are assigned to the PLS. |
UINT16 |
RW |
0x0000 (0dec) |
|
80A0:12 |
Default output |
If no valid table entry is available (counter value is >=0 but less than the first entry in the table), this value is output |
UINT16 |
RW |
0x0000 (0dec) |