ELM300x overview measurement ranges

Measurement

Connection technology

FSV

Mode

Maximum value/ value range

Voltage

2 wire

±30 V

Extended

±32.212.. V

Legacy

±30 V

±10 V

Extended

±10.737.. V

Legacy

±10 V

±5 V

Extended

±5.368.. V

Legacy

±5 V

±2.5 V

Extended

±2.684.. V

Legacy

±2.5 V

±1.25 V

Extended

±1.342.. V

Legacy

±1.25 V

±640 mV

Extended

±687.2.. mV

Legacy

±640 mV

±320 mV

Extended

±343.6.. mV

Legacy

±320 mV

±160 mV

Extended

±171.8.. mV

Legacy

±160 mV

±80 mV

Extended

±85.9.. mV

Legacy

±80 mV

±40 mV

Extended

±42.95.. mV

Legacy

±40 mV

±20 mV

Extended

±21.474.. mV

Legacy

±20 mV

Voltage

2 wire

+10 V

Extended

0…10.737.. V

Legacy

0…10 V

+5 V

Extended

0…5.368.. V

Legacy

0…5 V

ELM300x overview measurement ranges 1:
Fig.4: Overview measurement ranges, Bipolar
ELM300x overview measurement ranges 2:
Fig.7: Overview measurement ranges, Unipolar

Note: In Extended Range Mode the Underrange/Overrange display in the PDO status has the character of an information/warning when the nominal measuring range is exceeded, i.e. no Error is displayed in the PDO status and LED. If the technical measuring range is also exceeded, Error = TRUE is also displayed. The detection limit for Underrange/Overrange Error can be set in the CoE.

In Legacy Range mode, an Underrange/Overrange event also leads to an Error in the PDO status.