0x80n0 PAI Settings Ch.[n+1]

0 ≤ n ≤ m, n+1 = Channel number, m+1 = max. No. of channels

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

PAI Settings
Ch.[n+1]

 

UINT8

RO

0x41 (65dec)

80n0:01

Interface

Selection of the measurement configuration:

2 - U ±10 V
3 - U ±5 V
4 - U ±2.5 V
5 - U ±1.25 V
14 - U 0..10 V
15 - U 0..5 V
17 - I ±20 mA
18 - I 0..20 mA
19 - I 4..20 mA
20 - I 4..20 mA NAMUR

UINT16

RW

0x0002 (2dec)

80n0:04

Start Connection Test

Start connection test with rising edge (see section “Broken wire detection/ optional connection diagnosis”)

BOOLEAN

RW

0x00 (FALSE)

80n0:06

Enable Autorange

Autorange (Enable/ Disable)

BOOLEAN

RW

0x00 (FALSE)

80n0:09

Disable Offset Compensation

Offset Compensation (Enable/ Disable)

BOOLEAN

RW

0x00 (FALSE)

80n0:16

Filter 1

Options for filter 1:

0 – None
1 - FIR Notch 50 Hz
2 - FIR Notch 60 Hz
3 - FIR LP 100 Hz
4 - FIR LP 1000 Hz
5 - FIR HP 150 Hz
16 - IIR Notch 50 Hz
17 - IIR Notch 60 Hz
18 - IIR Butterw. LP 5th Ord. 1 Hz
19 - IIR Butterw. LP 5th Ord. 25 Hz
20 - IIR Butterw. LP 5th Ord. 100 Hz
21 - IIR Butterw. LP 5th Ord. 250 Hz
22 - IIR Butterw. LP 5th Ord. 1000 Hz
32 - User defined FIR Filter
33 - User defined IIR Filter
34 - User defined Average Filter

UINT16

RW

0x0000 (0dec)

80n0:17

Average Filter 1 No of Samples

Number of samples for user-defined Average Filter 1

UINT16

RW

0x0001 (1dec)

80n0:18

Decimation Factor

Factor of the individual sampling rate (min. 1)

UINT16

RW

0x0001 (1dec)

80n0:19

Filter 2

Options for filter 2:

0 – None
1 - IIR 1
2 - IIR 2
3 - IIR 3
4 - IIR 4
5 - IIR 5
6 - IIR 6
7 - IIR 7
8 - IIR 8
16 - User defined FIR Filter
17 - User defined IIR Filter
18 - User defined Average Filter

UINT16

RW

0x0000 (0dec)

80n0:1A

Average Filter 2 No of Samples

Number of samples for user-defined Average Filter 2

UINT16

RW

0x0001 (1dec)

80n0:1B

True RMS No. of Samples

Number of samples for "True RMS" calculation (min. 1, max. 1000);
also see chapter TrueRMS

UINT16

RW

0x0001 (1dec)

80n0:1C

Enable True RMS

Activation of "True RMS" calculation

BOOLEAN

RW

0x00 (FALSE)

80n0:1D

Enable Frequency Counter

Enable Frequency Counter

BOOLEAN

RW

0x00 (FALSE)

80n0:2B

Extended Functions

Options for future functions/settings
0 – Disabled

UINT16

RW

0x0000 (0dec)

80n0:2C

Integrator/Differentiator

Options:
0 – Off
1 – Integrator 1x
2 – Integrator 2x 1)
3 – Differentiator 1x
4 – Differentiator 2x 1)

UINT16

RW

0x0000 (0dec)

80n0:2D

Differentiator Samples Delta

Distance of samples for the differentiation; max. value = 1000

UINT16

RW

0x0001 (1dec)

80n0:2E

Scaler

Scaling (enum):
0 – Extended Range
1 – Linear
2 – Lookup Table
3 – Legacy Range
4 – Lookup Table (additive)

Optional:
5 Extended Functions

UINT16

RW

0x0000 (0dec)

80n0:2F

Lookup Table Length

Number of taps of the LookUp table

UINT16

RW

0x0064 (100dec)

80n0:30

Low Limiter

Smallest PDO output value

INT32

RW

0x80000000 (‑2147483648dec)

80n0:31

High Limiter

Largest PDO output value

INT32

RW

0x7FFFFFFF (2147483647dec)

80n0:32

Low Range Error

Lowest limit at which the error bit and the error LED are set

INT32

RW

0xFF800000
(‑8388608dec)

80n0:33

High Range Error

Highest limit at which the error bit and the error LED are set

INT32

RW

0x007FFFFF
(8388607dec)

80n0:34

Timestamp Correction

Value for correcting StartNextLatchTime (timestamp of the first sample)

INT32

RW

0x00000000
(0dec)

80n0:40

Filter 1 Type Info

Filter 1 type information

STRING

RW

N/A

80n0:41

Filter 2 Type Info

Filter 2 type information

STRING

RW

N/A

1) Functionality is only available from FW03