0x80n0 PAI Settings Ch.[n+1]

0 ≤ n ≤ m, n+1 = Channel number, m+1 = max. No. of channels

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

PAI Settings
Ch.[n+1]

 

UINT8

RO

0x41 (65dec)

80n0:01

Interface

Selection of the measurement configuration:
0 – None
1 - U ±60 V
2 - U ±10 V
3 - U ±5 V
4 - U ±2.5 V
5 - U ±1.25 V
6 - U ±640 mV
7 - U ±320 mV
8 - U ±160 mV
9 - U ±80 mV
10 - U ±40 mV
11 - U ±20 mV
14 - U 0..10 V
15 - U 0..5 V
17 - I ±20 mA
18 - I 0..20 mA
19 - I 4..20 mA
20 - I 4..20 mA NAMUR
more...

UINT16

RW

0x0000 (0dec)

80n0:02

Sensor Supply

Sensor supply:
0 - 0.0 V
1 - 0.5 V
2 - 1.0 V
3 - 1.5 V
4 - 2.0 V
5 - 2.5 V
6 - 3.0 V
7 - 3.5 V
8 - 4.0 V
9 - 4.5 V
10 - 5.0 V
65534 - Local Control
65535 - External Supply

UINT16

RW

0x0000 (0dec)

80n0:03

IEPE AC Coupling

0 - Off (DC Coupling)
1 - 0.001 Hz
2 - 0.01 Hz
3 - 0.1 Hz
4 - 1 Hz
5 - 10 Hz

UINT16

RW

0x0000 (0dec)

80n0:04

Start Connection Test

Start connection test with rising edge (see section Connection test/switchable connection diagnosis)

BOOLEAN

RW

0x00 (FALSE)

80n0:05

Coldjunction Compensation

0 - Intern
1 - None
2 - Extern Processdata
3 - Fix Value

UINT8

RW

0x00 (0dec)

80n0:06

Enable Autorange

Autorange (Enable/ Disable)

BOOLEAN

RW

0x00 (FALSE)

80n0:07

IEPE Bias Current

0 - 0 mA
1 - 2 mA
2 - 4 mA

BIT4

RW

0x00 (0dec)

80n0:08

Enable Shunt Calibration

Shunt calibration (Enable/ Disable)

BOOLEAN

RW

0x00 (FALSE)

80n0:13

Wire Resistance Compensation

Wire resistance compensation

REAL32

RW

0x00000000 (0dec)

80n0:14

RTD Element

0 – None
1 - PT100 (-200...850°C)
2 - NI100 (-60...250°C)
3 - PT1000 (-200...850°C)
4 - PT500 (-200...850°C)
5 - PT200 (-200...850°C)
6 - NI1000 (-60...250°C)
7 - NI1000 TK5000 (-30...160°C)
8 - NI120 (-60...320°C)
9 - KT100/110/130/210/230
KTY10/11/13/16/19
(-50...150°C)
10 - KTY81/82-110,120,150 (-50...150°C)
11 - KTY81-121 (-50...150°C)
12 - KTY81-122 (-50...150°C)
13 - KTY81-151 (-50...150°C)
14 - KTY81-152 (-50...150°C)
15 - KTY81/82-210,220,
250 (-50...150°C)
16 - KTY81-221 (-50...150°C)
17 - KTY81-222 (-50...150°C)
18 - KTY81-251 (-50...150°C)
19 - KTY81-252 (-50...150°C)
20 - KTY83-110,120,150
(-50...175°C)
21 - KTY83-121 (-50...175°C)
22 - KTY83-122 (-50...175°C)
23 - KTY83-151 (-50...175°C)
24 - KTY83-152 (-50...175°C)
25 - KTY84-130,150
(-40...300°C)
26 - KTY84-151 (-40...300°C)
27 - KTY21/23-6 (-50...150°C)
28 - KTY1x-5 (-50...150°C)
29 - KTY1x-7 (-50...150°C)
30 - KTY21/23-5 (-50...150°C)
31 - KTY21/23-7 (-50...150°C)
64 - B-Parameter Equation
(8006)
65 - DIN IEC 60751 Equation
(8006)
66 - Steinhart Hart Equation
(8006)

UINT16

RW

0x0000 (0dec)

80n0:15

TC Element

0 – None
1 - K -270...1372°C
2 - J -210...1200°C
3 - L -50...900°C
4 - E -270...1000°C
5 - T -270...400°C
6 - N -270...1300°C
7 - U -50...600°C
8 - B 200...1820°C
9 - R -50...1768°C
10 - S -50...1768°C
11 - C 0...2320°C
13 – D 0...2490°C
14 – G 1000...2300°C
15 – P (PLII) 0...1395°C
16 - Au/Pt 0...1000°C
17 – Pt/Pd 0...1500°C
18 – A-1 0...2500°C
19 – A-2 0...1800°C
20 – A-3 0...1800°C

UINT16

RW

0x0000 (0dec)

80n0:16

Filter 1

Options for filter 1:

0 – None
1 - FIR Notch 50 Hz
2 - FIR Notch 60 Hz
3 - FIR LP 100 Hz
4 - FIR LP 1000 Hz
5 - FIR HP 150 Hz
16 - IIR Notch 50 Hz
17 - IIR Notch 60 Hz
18 - IIR Butterw. LP 5th Ord. 1 Hz
19 - IIR Butterw. LP 5th Ord. 25 Hz
20 - IIR Butterw. LP 5th Ord. 100 Hz
21 - IIR Butterw. LP 5th Ord. 250 Hz
22 - IIR Butterw. LP 5th Ord. 1000 Hz
32 - User defined FIR Filter
33 - User defined IIR Filter
34 - User defined Average Filter

UINT16

RW

0x0000 (0dec)

80n0:17

Average Filter 1 No of Samples

Number of samples for user-defined Average Filter 1

UINT16

RW

0x0001 (1dec)

80n0:18

Decimation Factor

Factor of the individual sampling rate (min. 1)

UINT16

RW

0x0001 (1dec)

80n0:19

Filter 2

Options for filter 2:
0 – None
1 - IIR 1
2 - IIR 2
3 - IIR 3
4 - IIR 4
5 - IIR 5
6 - IIR 6
7 - IIR 7
8 - IIR 8
16 - User defined FIR Filter
17 - User defined IIR Filter
18 - User defined Average Filter

UINT16

RW

0x0000 (0dec)

80n0:1A

Average Filter 2 No of Samples

Number of samples for user-defined Average Filter 2

UINT16

RW

0x0001 (1dec)

80n0:1B

True RMS No. of Samples

Number of samples for "True RMS" calculation (min. 1, max. 1000);
also see True RMS

UINT16

RW

0x0001 (1dec)

80n0:1C

Enable True RMS

Activation of "True RMS" calculation

BOOLEAN

RW

0x00 (FALSE)

80n0:1D

Enable Frequency Counter

Enable Frequency Counter

BOOLEAN

RW

0x00 (FALSE)

80n0:1E

Reset Load Cycle Counter

Reset Load Cycle Counter

BOOLEAN

RW

0x00 (FALSE)

80n0:2B

Extended Functions

Options for future functions/settings
0 – Disabled
1 – Load Cell Analysis

UINT16

RW

0x0000 (0dec)

80n0:2C

Integrator/Differentiator

Options:
0 – Off
1 – Integrator 1x
2 – Integrator 2x 1)
3 – Differentiator 1x
4 – Differentiator 2x 1)

UINT16

RW

0x0000 (0dec)

80n0:2D

Differentiator Samples Delta

Distance of samples for the differentiation; max. value = 1000; except ELM36xx with max value = 5000

UINT16

RW

0x0001 (1dec)

80n0:2E

Scaler

Scaling (enum):
0 – Extended Range
1 – Linear
2 – Lookup Table
3 – Legacy Range
4 – Lookup Table (additive)

Optional:
5 – Extended Function
6 - Temperature Celsius
7 - Temperature Kelvin
8 - Temperature Fahrenheit

UINT16

RW

0x0000 (0dec)

80n0:2F

Lookup Table Length

Number of taps of the LookUp table

UINT16

RW

0x0064 (100dec)

80n0:32

Low Range Error

Lowest limit at which the error bit and the error LED are set

INT32

RW

0xFF800000
(‑8388608dec)

80n0:33

High Range Error

Highest limit at which the error bit and the error LED are set

INT32

RW

0x007FFFFF
(8388607dec)

80n0:34

Timestamp Correction

Value for correcting StartNextLatchTime (timestamp of the first sample)

INT32

RW

0xFFFB6C20
(‑300000dec)

80n0:35

Low Limiter

Smallest PDO output value

REAL32

RW

0xFF7FFFFD
(-3.4028231e+38)

80n0:36

High Limiter

Largest PDO output value

REAL32

RW

0x7F7FFFFD
(3.4028231e+38)

80n0:37

Bridge Resistance

Bridge resistance

REAL32

RW

0x43AF0000
(350.0)

80n0:38

Wire Resistance neg. Supply

Wire Resistance neg. Supply

REAL32

RW

0x00000000 (0dec)

80n0:39

Wire Resistance pos. Supply

Wire Resistance pos. Supply

REAL32

RW

0x00000000 (0dec)

80n0:3A

Low Load Cycle Limit

Low load cycle limit

REAL32

RW

0x00000000 (0dec)

80n0:3B

High Load Cycle Limit

High load cycle limit

REAL32

RW

0x00000000 (0dec)

80n0:3C

TC CJ Value

Value of the cold junction

REAL32

RW

0x00000000 (0dec)

80n0:40

Filter 1 Type Info

Filter 1 type information

STRING

RW

N/A

80n0:41

Filter 2 Type Info

Filter 2 type information

STRING

RW

N/A

1) Functionality is only available from FW03