Measurement ±10 V
Measurement mode |
±10 V | |||
---|---|---|---|---|
Measuring range, nominal |
-10…+10 V | |||
Measuring range, end value (FSV) |
10 V | |||
Measuring range, technically usable |
-10.737…+10.737 V | |||
PDO resolution (including sign) |
24 bit |
16 bit 2) | ||
PDO LSB (Extended Range) |
1.28 µV |
327.68 µV | ||
PDO LSB (Legacy Range) |
1.192.. µV |
305.18.. µV | ||
Basic accuracy: Measuring deviation at 23°C, with averaging, typ. 1) |
< ±0.015 %, < ±150 ppmFSV < ±1.5 mV | |||
Extended basic accuracy: Measuring deviation at 0…55°C, with averaging, typ. 1) 6) |
< ±0.023 %, < ±230 ppmFSV < ±2.3 mV | |||
Offset/Zero point deviation (at 23°C) 1) |
EOffset |
< 30 ppmFSV | ||
Gain/scale/amplification deviation (at 23°C) 1) |
EGain |
< 140 ppm | ||
Non-linearity over the whole measuring range 1) |
ELin |
< 40 ppmFSV | ||
Repeatability, over 24 h, with averaging 1) |
ERep |
< 20 ppmFSV | ||
Temperature coefficient, typ. 1) |
TcGain |
< 5 ppm/K | ||
TcOffset |
< 2 ppmFSV/K < 20 µV/K | |||
Largest short-term deviation during a specified electrical interference test |
±0.03% = 300 ppmFSV typ. | |||
Input impedance ±Input 1 (internal resistance)
|
Differential typ. approx. 4.12 MΩ || 11 nF CommonMode typ. approx. 40 nF against SGND |
1) valid for ELM3504-00x0 since HW06, ELM3502-00x0 since HW05
2) The analog measurement is always done with 24 bits, in 16-bit mode the eight least significant bits are cut off. For further information see chapter “Commissioning”/ “Process data overview”
6) Calculated value according to equation in chapter "General information on measuring accuracy/measurement uncertainty" for quick estimation of usability over the specified ambient temperature range in operation (Tambient). In real use, for example at a relatively constant ambient temperature Tambient, a lower (better) achievable uncertainty is attained. A specific calculation according to chapter "General information on measuring accuracy/measurement uncertainty" is recommended, especially if the instrument allows a wider ambient temperature range in operation than 0...55 °C.
ELM3502 (20 ksps)
Noise (without filtering) |
ENoise, PtP |
< 80 ppmFSV |
< 625 digits |
< 0.80 mV |
ENoise, RMS |
< 13 ppmFSV |
< 102 digits |
< 130.00 µV | |
Max. SNR |
> 97.7 dB | |||
Noisedensity@1kHz |
< 1.30 | |||
Noise (with 50 Hz FIR filter) |
ENoise, PtP |
< 9 ppmFSV |
< 70 digits |
< 90.00 µV |
ENoise, RMS |
< 1.5 ppmFSV |
< 12 digits |
< 15.00 µV | |
Max. SNR |
> 116.5 dB |
ELM3504 (10 ksps)
Noise (without filtering) |
ENoise, PtP |
< 60 ppmFSV |
< 469 digits |
< 0.60 mV |
ENoise, RMS |
< 10 ppmFSV |
< 78 digits |
< 100.00 µV | |
Max. SNR |
> 100.0 dB | |||
Noisedensity@1kHz |
< 1.41 | |||
Noise (with 50 Hz FIR filter) |
ENoise, PtP |
< 9 ppmFSV |
< 70 digits |
< 90.00 µV |
ENoise, RMS |
< 1.5 ppmFSV |
< 12 digits |
< 15.00 µV | |
Max. SNR |
> 116.5 dB |
Preliminary specifications:
Measurement mode |
±10 V | ||
---|---|---|---|
Common-mode rejection ratio (without filter) |
DC: >115 dB typ. |
50 Hz: >105 dB typ. |
1 kHz: >80 dB typ. |
Common-mode rejection ratio (with 50 Hz FIR filter) |
DC: >115 dB typ. |
50 Hz: >115 dB typ. |
1 kHz: >115 dB typ. |

Note: In Extended Range Mode the Underrange/Overrange display in the PDO status has the character of an information/warning when the nominal measuring range is exceeded, i.e. no Error is displayed in the PDO status and LED. If the technical measuring range is also exceeded, Error = TRUE is also displayed. The detection limit for Underrange/Overrange Error can be set in the CoE. In Legacy Range mode, an Underrange/Overrange event also leads to an Error in the PDO status. |