Sample program 5 (write filter coefficients)
Download TwinCAT 3 project: program link
Program description
Transmission of exemplary filter coefficients via CoE access into the Klemme.
![]() | General settings
|
Variable declaration sample program 5
PROGRAM MAIN
// Variable declaration example program 5
VAR CONSTANT
NumOfFilterCoeff :BYTE:=40;
END_VAR
VAR
// Function block of library "Tc2_EtherCAT" for CoE Object access:
fb_coe_write :FB_EcCoESdoWrite;
userNetId :T_AmsNetId := '???';
userSlaveAddr :UINT := ???;
// Writing PLC state for coefficients transfer (Set to 0 for start)
wState :BYTE:=255;
index :BYTE:=1; // Start index for coefficients transfer
wCoEIndexUserFilterCoeffizents :WORD:=16#8001;
aFilterCoeffs:ARRAY[0..NumOfFilterCoeff] OF LREAL :=
[
// Example filter coefficients FIR band pass: 3600..3900 Hz
// Usage: "User defined FIR Filter" (32)
0.03663651655662163,
0.04299467480848277,
-0.007880289104928245,
0.0664029021294729,
-0.0729038234874446,
-0.00005849791174519834,
0.05628409460964408,
-0.0525134329294473,
0.026329003448584205,
0.00027114381194760643,
-0.03677629552114248,
0.06743018479714939,
-0.0560894442193289,
0.0009722394088121363,
0.05676876756757213,
-0.07775650809213645,
0.05330627422911416,
0.0009941073749156226,
-0.055674804078696793,
0.07874009379691002,
-0.055674804078696793,
0.0009941073749156226,
0.05330627422911416,
-0.07775650809213645,
0.05676876756757213,
0.0009722394088121363,
-0.0560894442193289,
0.06743018479714939,
-0.03677629552114248,
0.00027114381194760643,
0.026329003448584205,
-0.0525134329294473,
0.05628409460964408,
-0.00005849791174519834,
-0.0729038234874446,
0.0664029021294729,
-0.007880289104928245,
0.04299467480848277,
0.03663651655662163,
0
];
nValue :DINT; // Temporary variable
END_VARExecution part:
// Example program 5:
// writes filter coefficients of
// "User defined FIR Filter" (32)
// incl. example coefficients for band pass
// Note: writing possible, if CoE Object
// PAI Settings Ch.1 (0x8000:16) has value 32 or 33 set, only!
// (32 = User defined FIR Filter / 33 = User defined IIR Filter)
// ===============================================================
CASE wState OF
0:
fb_coe_write(bExecute := FALSE);// Prepare CoE access
wState := wState + 1;// Go to next state
1:
//nValue := REAL_TO_DINT(DINT_TO_REAL(aFilterCoeffs[index]) *16384);
nValue := LREAL_TO_DINT(aFilterCoeffs[index] * 1073741824); // Bit-shift factor: 2^30
// Write filter coefficients (max. 40 entries)
fb_coe_write(
sNetId:= userNetId,
nSlaveAddr:= userSlaveAddr,
nSubIndex:= index,
nIndex:= wCoEIndexUserFilterCoeffizents,
pSrcBuf:= ADR(nValue),
cbBufLen:= SIZEOF(nValue),
bExecute:= TRUE,
tTimeout:= T#1S
);
wState := wState + 1; // Go to next state
2:
// Execute writing to CoE
fb_coe_write();
IF fb_coe_write.bError THEN
wState := 100; // Error case
ELSE
IF NOT fb_coe_write.bBusy THEN
index := index + 1;
IF index <= (NumOfFilterCoeff) THEN
fb_coe_write(bExecute := FALSE);// Prepare the next CoE access
wState := 1;// Write next value
ELSE
wState := 255;// Done
END_IF
END_IF
END_IF
100:
; // Error handling
255:
; // Go on..
END_CASE