0x80n6 PAI Scaler Settings Ch.[n+1]

0 ≤ n ≤ m, n+1 = channel number; m+1 = max. number of channels

Index (hex)

Name

Meaning

Data type

Flags

Default

80n6:0

PAI scaler settings
ch.[n+1]

Scaling values offset/gain or LookUp table with 100 x/y value pairs

UINT8

RO

0xC8 (200dec)

80n6:01

Scaler offset/
scaler value 1

Scaling offset
or LookUp x-value 1

REAL32

RW

0x00000000 (0dec)

80n6:02

Scaler gain/
scaler value 2

Scaling gain
or LookUp y-value 1

REAL32

RW

0x00000000 (0dec)

80n6:03

Scaler value 3

LookUp x-value 2

REAL32

RW

0x00000000 (0dec)

80n6:04

Scaler value 4

LookUp y-value 2

REAL32

RW

0x00000000 (0dec)

..

..

..

..

..

..

80n6:C7

Scaler value 199

LookUp x-value 100

REAL32

RW

0x00000000 (0dec)

80n6:C8

Scaler value 200

LookUp y-value 100

REAL32

RW

0x00000000 (0dec)