ELM3002-02x5/ ELM3002-03x5/ ELM3002-04x5 overview measurement ranges

Measurement

Connection

FSV / interface

Mode

displayed maximum value/value range

ELM3002-02x5

ELM3002-03x5

ELM3002-04x5

Voltage

2-wire

±1200 V With Extended Overrange **)

Extended 400% *)

approx. ±5 kV

Channel 1

Channel 2

-

Channel 1

only

Legacy ***)

approx. ±5 kV

±1200 V

Extended 107% *)

±1288.44.. V

Channel 1

Channel 2

-

Channel 1

only

Legacy

±1200 V

±600 V

Extended 107% *)

±644.22.. V

Channel 1

Channel 2

-

Channel 1

only

Legacy

±600 V

±360 V

Extended 107% *)

±386.532.. V

Channel 1

Channel 2

-

Channel 1

only

Legacy

±360 V

±60 V

Extended 107% *)

±64.422.. V

Channel 1

Channel 2

-

Channel 1

only

Legacy

±60 V

*) The measurement uncertainty in overrange is not specified.

**) Voltages > 1200 V only intended for the purpose of transient monitoring, not as a permanent measurement voltage, channel measures up to the technical FSV

***) In ±1200 V with Extended Overrange, Legacy corresponds to 0x007FFFFF ~ 1200 V, but in contrast to the other legacy modes, overrange is also measured up to the specified maximum value, see the following diagram

Measurement

Connection

FSV / interface

Mode

displayed maximum value/value range

ELM3002-02x5

ELM3002-03x5

ELM3002-04x5

Voltage

2-wire

±5 V

Extended
107%

±5.368.. V

-

Channel 1

Channel 2

Channel 2

only

Legacy

±5 V

±2.5 V

Extended
107%

±2.684.. V

-

Channel 1

Channel 2

Channel 2

only

Legacy

±2.5 V

±1 V

Extended 107%

±1.0737.. V

-

Channel 1

Channel 2

Channel 2

only

Legacy

±1V

±250 mV

Extended 107%

±268.43..mV

-

Channel 1

Channel 2

Channel 2

only

Legacy

±250 mV

±150 mV

Extended 107%

±161.06..mV

-

Channel 1

Channel 2

Channel 2

only

Legacy

±150 mV

±100 mV

Extended 107%

±107.37.. mV

-

Channel 1

Channel 2

Channel 2

only

Legacy

±100 mV

±60 mV

Extended 107%

±64.42.. mV

-

Channel 1

Channel 2

Channel 2

only

Legacy

±60 mV

ELM3002-02x5/ ELM3002-03x5/ ELM3002-04x5 overview measurement ranges 1:
Fig.4: Overview measurement ranges, bipolar
ELM3002-02x5/ ELM3002-03x5/ ELM3002-04x5 overview measurement ranges 2:
Fig.25: Overview measurement ranges, bipolar (FSV Range, 400%)

Note: In Extended Range Mode the Underrange/Overrange display in the PDO status has the character of an information/warning when the nominal measuring range is exceeded, i.e. no Error is displayed in the PDO status and LED. If the technical measuring range is also exceeded, Error = TRUE is also displayed. The detection limit for Underrange/Overrange Error can be set in the CoE.

In Legacy Range mode, an Underrange/Overrange event also leads to an Error in the PDO status.