0x70n0 PAI Control Ch.[n+1]
0 ≤ n ≤ m, n+1 = Channel number, m+1 = max. No. of channels
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
70n0:0 |
PAI Control |
|
UINT8 |
RO |
0x02 (2dec) |
|
70n0:01 |
Integrator Reset |
Restart of the integration with each positive edge |
BOOLEAN |
RO |
0x00 (FALSE) |
|
70n0:02 |
Peak Hold Reset |
Start new peak value detection with each positive edge |
BOOLEAN |
RO |
0x00 (FALSE) |
|
70n0:03 |
Sensor Supply Disable |
Sensor Supply disabled 1) |
BOOLEAN |
RO |
0x00 (FALSE) |
|
70n0:04 |
Tare |
Triggering the tare function at each positive edge 1) |
BOOLEAN |
RO |
0x00 (FALSE) |
1) available from revision -0020