ELM334x overview measurement ranges

Measurement

Connection technology

FSV

Mode

Maximum value/ value range

Voltage

2-wire

±320 mV

REAL32

±343.6.. mV

INT32 Extended

±343.6.. mV

INT32 Legacy

±320 mV

±80 mV

REAL32

±85.9.. mV

INT32 Extended

±85.9.. mV

INT32 Legacy

±80 mV

±40 mV

REAL32

±42.95.. mV

INT32 Extended

±42.95.. mV

INT32 Legacy

±40 mV

±20 mV

REAL32

±21.474.. mV

INT32 Extended

±21.474.. mV

INT32 Legacy

±20 mV

Temperature thermocouple (TC)

2-wire

±80 mV

Temperature 0.01°C

Depending on type up to 2320°C

ELM334x overview measurement ranges 1:
Fig.4: Overview measurement ranges, Bipolar
ELM334x overview measurement ranges 2:
Fig.7: Overview measurement ranges, Unipolar

Note: In Extended Range Mode the Underrange/Overrange display in the PDO status has the character of an information/warning when the nominal measuring range is exceeded, i.e. no Error is displayed in the PDO status and LED. If the technical measuring range is also exceeded, Error = TRUE is also displayed. The detection limit for Underrange/Overrange Error can be set in the CoE.

In Legacy Range mode, an Underrange/Overrange event also leads to an Error in the PDO status.