Assembly of the LEMO connector ELM3702-0101
Mounting guideline for Mode 2 “RTD in LEMO connector”
RTD: PT1000 F0.1 (1/3 DIN B), dimension 2.5x2x1.3mm, JUMO PCA 1.2003.10M
![Assembly of the LEMO connector ELM3702-0101 1:](Images/png/9729732363__en-US__Web.png)
The PT1000 is connected between pin 4 (-Input2) and pin 5 (+Uv).
![Assembly of the LEMO connector ELM3702-0101 2:](Images/png/10223573771__Web.png)
TC wire and RTD must be connected by crimping:
![Assembly of the LEMO connector ELM3702-0101 3:](Images/png/10223602315__Web.png)
After electrical installation, 2K Epoxy sealing compound is required.
A detailed manual “Usage of external cold junction within LEMO connectors for ELM3xxx“ can be requested by the Beckhoff support.