EL9550-0010 - Connection, LEDs and process data

EL9550-0010 - Connection, LEDs and process data 1:
Fig.46: EL9550-0010

LED

Color

Meaning

Power-LED field

green

off

24 VDC - field supply not available

on

24 VDC - field supply available

Power-LED system

green

off

24 VDC - system supply not available

on

24 VDC - system supply available

Us Low LED

red

off

no error

on

Undervoltage, Us below 18 V

Up Low LED

red

off

no error

on

Undervoltage, Up below 18 V

RUN

green

These LEDs indicate the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal

Flashing
(2 Hz)

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set

Flashing
(1 Hz)

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

Flashing
(10 Hz)

State of the EtherCAT State Machine: BOOTSTRAP = function for Firmware updates of the terminal, for example

Terminal point

Description

Name

No.

Output +24 V system

1

Output +24 V (system)

Input +24 V field

2

Input +24 V (field)

Input 0 V field

3

Input 0 V (field)

Input +24 V system

4

Input +24 V (system)

Output 0 V system

5

Output 0 V (system)

Input +24 V field

6

Input +24 V (field) (internally connected to positive power contact)

Input 0 V field

7

Input 0 V (field) (internally connected to negative power contact)

Input 0 V system

8

Input 0 V (system)

Process data EL9550-0010

The EL9550-0010 has a bit width of 4 bits (diagnostic bits for Up/Us undervoltage and overvoltage) in the process image and is represented in the TwinCAT tree as follows:

EL9550-0010 - Connection, LEDs and process data 2:
Fig.47: EL9550-0010 in the TwinCAT tree