Installation instructions for enhanced mechanical load capacity
  | |
Risk of injury through electric shock and damage to the device! Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals!  | 
Additional checks
The terminals have undergone the following additional tests:
Verification  | Explanation  | 
|---|---|
Vibration  | 10 frequency runs in 3 axes  | 
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude  | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude  | |
Shocks  | 1000 shocks in each direction, in 3 axes  | 
25 g, 6 ms  | 
Additional installation instructions and notes
For terminals with enhanced mechanical load capacity, the following additional installation instructions and notes apply:
- The enhanced mechanical load capacity is valid for all permissible installation positions.
 - Use a mounting rail according to EN 60715 TH35-15.
 - Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth terminal or reinforced end clamp.
 - The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting width) or 32 terminals (24 mm mounting width) - Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of the rail.
 - The mounting points of the mounting rail must be set at 5 cm intervals.
 - Use countersunk head screws to fasten the mounting rail.
 - The free length between the strain relief and the wire connection should be kept as short as possible. A distance of approx. 10 cm should be maintained to the cable duct.
 
