Application example
| |
Risk of injury through electric shock and damage to the device! Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals! |
Function example
- The capacitor in the EL9576 compensates peaks in the supply voltage for the stepper motor/DC motor.
- As soon as this supply voltage exceeds the set threshold value (standard 50 V), the EL9576 switches the brake resistor REXTERNAL on, which then converts the brake energy fed back from the stepper motor / DC motor connected to the EL7041 into thermal energy.
- An additional power supply via the E-bus is necessary for this function!

![]() | Connection option for several motors An EL9576 Capacitor Terminal can condition the supply voltage for several motors. |
Notice | |
Dimensioning of the brake resistor The brake resistor REXTERNAL (typically 10 Ω) should be dimensioned such that it can withstand the expected heat development without damage! |