UL notice
| ||
![]() | Application Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT System only. | |
| ||
![]() | Examination For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire and electrical shock (in accordance with UL508 and CSA C22.2 No. 142). | |
| ||
![]() | For devices with Ethernet connectors Not for connection to telecommunication circuits. | |
| ||
![]() | Operating of the Beckhoff Terminal EL9260 with Beckhoff Terminal EL1702-0020 Fuses have to be specified as 250Vac/6.3A/size 20x5.2mm as all of these parameters are critical for safety. | |
Basic principles
UL certification according to UL508. Devices with this kind of certification are marked by this sign:


