Information and diagnostic data

Index 1020 Device Statistics

Index (hex)

Name

Meaning

Data type

Flags

Default

1020:0

Device Statistics

Max. Subindex

UINT8

RO

0x03 (3dec)

1020:01

Time since power on

Operating time since last power-on [s]

UINT32

RO

0x00000000 (0dec)

1020:02

Total time powered

Total operating time [s]

UINT32

RO

0x00000000 (0dec)

1020:03

Number of power cycles

Number of power cycles

UINT32

RO

0x00000000 (0dec)

Index 9000 AO Output Internal Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9000:0

AO Output Internal Data

Max. Subindex

UINT8

RO

0x0F (15dec)

9000:01

Value after User Scale

Current output value after UserScale, see data flow, chapter "Analog output commissioning"

REAL32

RO

0x00000000 (0.0)

9000:02

Warning Low Counter

Counter for "Warning Low" events

UINT32

RO

0x00000000 (0dec)

9000:03

Warning High Counter

Counter for "Warning High" events

UINT32

RO

0x00000000 (0dec)

9000:05

Watchdog Counter

Counter for "Watchdog" events

UINT32

RO

0x00000000 (0dec)

9000:06

Limiter Low Counter

Counter for "Limiter Low" events

UINT32

RO

0x00000000 (0dec)

9000:07

Limiter High Counter

Counter for "Limiter High" events

UINT32

RO

0x00000000 (0dec)

9000:08

Value After Slew Rate Limitation

Current output value after SlewRateLimitation, see data flow, chapter "Analog output commissioning"

REAL32

RO

0x00000000 (0.0)

9000:0A

Value After User Calibration

Current output value after user adjustment, see data flow, chapter "Commissioning analog output"

REAL32

RO

0x00000000 (0.0)

9000:0B

Value After Vendor Calibration

Current output value after vendor adjustment, see data flow, chapter "Analog output commissioning"

REAL32

RO

0x00000000 (0.0)

9000:0C

DAC Raw Value

Output value to the DAC

INT32

RO

0x00000000 (0dec)

9000:0F

Output Cycle Counter Error

Counter for "Output Cycle Counter Error" events

UINT32

RO

0x00000000 (0dec)

Index 9002 AO Output Info Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9002:0

AO Output Info Data

Max. Subindex

UINT8

RO

0x12 (18dec)

9002:11

Vendor Calibration Counter

Counter for changes to the vendor adjustment data

UINT32

RO

0x00000000 (0dec)

9002:12

User Calibration Counter

Counter for changes to the user calibration data

UINT32

RO

0x00000000 (0dec)

Index 9010 AO Complementary Limit High Internal Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9010:0

AO Complementary Limit High Internal Data

Max. Subindex

UINT8

RO

0x0F (15dec)

9010:02

Warning Low Counter

Counter for "Warning Low" events

UINT32

RO

0x00000000 (0dec)

9010:03

Warning High Counter

Counter for "Warning High" events

UINT32

RO

0x00000000 (0dec)

9010:06

Limiter Low Counter

Counter for "Limiter Low" events

UINT32

RO

0x00000000 (0dec)

9010:07

Limiter High Counter

Counter for "Limiter High" events

UINT32

RO

0x00000000 (0dec)

9010:0A

Value After User Calibration

Current output value after user adjustment

REAL32

RO

0x00000000 (0.0)

9010:0B

Value After Vendor Calibration

Current output value after manufacturer adjustment

REAL32

RO

0x00000000 (0.0)

9010:0F

Output Cycle Counter Error

Counter for "Output Cycle Counter Error" events

UINT32

RO

0x00000000 (0dec)

Index 9012 AO Complementary Limit High Info Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9012:0

AO Complementary Limit High Info Data

Max. Subindex

UINT8

RO

0x12 (18dec)

9012:11

Vendor Calibration Counter

Counter for changes to the vendor adjustment data

UINT32

RO

0x00000000 (0dec)

9012:12

User Calibration Counter

Counter for changes to the user calibration data

UINT32

RO

0x00000000 (0dec)

Index 9030 AI Input Voltage Internal Data*)

Index (hex)

Name

Meaning

Data type

Flags

Default

9030:0

AI Input Voltage Internal Data

Max. Subindex

UINT8

RO

0x1B (27dec)

9030:02

ADC raw value

ADC raw data, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9030:03

Value After Filter 1

Current measured value after filter 1, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9030:04

Value After Interface

Current measured value after interface evaluation, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9030:05

Value After Vendor Calibration

Current measured value after vendor adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9030:06

Value After User Calibration

Current measured value after user adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9030:0B

Value After User Scale

Current measured value according to UserScale, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9030:0C

Actual positive peak hold

 Positive drag indicator, instantaneous value

REAL32

RO

0x00000000 (0.0)

9030:0D

Actual negative peak hold

 Negative drag indicator, instantaneous value

REAL32

RO

0x00000000 (0.0)

9030:14

Underrange Error Counter

 Counter for underrange errors

UINT32

RO

0x00000000 (0dec)

9030:15

Overrange Error Counter

 Counter for overrange errors

UINT32

RO

0x00000000 (0dec)

9030:16

Limit 1 Counter Low

 Counter for "Limit 1 Low" events

UINT32

RO

0x00000000 (0dec)

9030:17

Limit 1 Counter High

  Counter for "Limit 1 High" events

UINT32

RO

0x00000000 (0dec)

9030:18

Limit 2 Counter Low

  Counter for "Limit 2 Low" events

UINT32

RO

0x00000000 (0dec)

9030:19

Limit 2 Counter High

  Counter for "Limit 2 High" events

UINT32

RO

0x00000000 (0dec)

9030:1A

Tare Value

 Tare value currently taken into account

REAL32

RO

0x00000000 (0.0)

9030:1B

Sampling rate

 Current effective sampling rate, [1/sec]

REAL32

RO

0x00000000 (0.0)

*) only for EL9501

Index 9032 AI Input Voltage Info Data*)

Index (hex)

Name

Meaning

Data type

Flags

Default

9032:0

AI Input Voltage Info Data

Max. Subindex

UINT8

RO

0x12 (18dec)

9032:11

Vendor Calibration Counter

Counter for changes to the vendor adjustment data

UINT32

RO

0x00000000 (0dec)

9032:12

User Calibration Counter

Counter for changes to the user calibration data

UINT32

RO

0x00000000 (0dec)

*) only for EL9501

Index 9050 AI Output Voltage Internal Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9050:0

AI Output Voltage Internal Data

Max. Subindex

UINT8

RO

0x1B (27dec)

9050:02

ADC raw value

ADC raw data, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9050:03

Value After Filter 1

Current measured value after filter 1, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9050:04

Value After Interface

Current measured value after interface evaluation, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9050:05

Value After Vendor Calibration

Current measured value after vendor adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9050:06

Value After User Calibration

Current measured value after user adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9050:0B

Value After User Scale

Current measured value according to UserScale, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9050:0C

Actual positive peak hold

 Positive drag indicator, instantaneous value

REAL32

RO

0x00000000 (0.0)

9050:0D

Actual negative peak hold

 Negative drag indicator, instantaneous value

REAL32

RO

0x00000000 (0dec)

9050:14

Underrange Error Counter

 Counter for underrange errors

UINT32

RO

0x00000000 (0dec)

9050:15

Overrange Error Counter

 Counter for overrange errors

UINT32

RO

0x00000000 (0dec)

9050:16

Limit 1 Counter Low

 Counter for "Limit 1 Low" events

UINT32

RO

0x00000000 (0dec)

9050:17

Limit 1 Counter High

  Counter for "Limit 1 High" events

UINT32

RO

0x00000000 (0dec)

9050:18

Limit 2 Counter Low

  Counter for "Limit 2 Low" events

UINT32

RO

0x00000000 (0dec)

9050:19

Limit 2 Counter High

  Counter for "Limit 2 High" events

UINT32

RO

0x00000000 (0dec)

9050:1A

Tare Value

 Tare value currently taken into account

REAL32

RO

0x00000000 (0.0)

9050:1B

Sampling rate

 Current effective sampling rate, [1/sec]

REAL32

RO

0x00000000 (0.0)

Index 9052 AI Output Voltage Info Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9052:0

AI Output Voltage Info Data

Max. Subindex

UINT8

RO

0x12 (18dec)

9052:11

Vendor Calibration Counter

Counter for changes to the vendor adjustment data

UINT32

RO

0x00000000 (0dec)

9052:12

User Calibration Counter

Counter for changes to the user calibration data

UINT32

RO

0x00000000 (0dec)

Index 9060 AI Output Current Internal Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9060:0

AI Output Current Internal Data

Max. Subindex

UINT8

RO

0x1B (27dec)

9060:02

ADC raw value

ADC raw data, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9060:03

Value After Filter 1

Current measured value after filter 1, see data flow, chapter "Analog input commissioning"

INT32

RO

0x00000000 (0dec)

9060:04

Value After Interface

Current measured value after interface evaluation, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9060:05

Value After Vendor Calibration

Current measured value after vendor adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9060:06

Value After User Calibration

Current measured value after user adjustment, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9060:0B

Value After User Scale

Current measured value according to UserScale, see data flow, chapter "Analog input commissioning"

REAL32

RO

0x00000000 (0.0)

9060:0C

Actual positive peak hold

 Positive drag indicator, instantaneous value

REAL32

RO

0x00000000 (0.0)

9060:0D

Actual negative peak hold

 Negative drag indicator, instantaneous value

REAL32

RO

0x00000000 (0dec)

9060:14

Underrange Error Counter

 Counter for underrange errors

UINT32

RO

0x00000000 (0dec)

9060:15

Overrange Error Counter

 Counter for overrange errors

UINT32

RO

0x00000000 (0dec)

9060:16

Limit 1 Counter Low

 Counter for "Limit 1 Low" events

UINT32

RO

0x00000000 (0dec)

9060:17

Limit 1 Counter High

  Counter for "Limit 1 High" events

UINT32

RO

0x00000000 (0dec)

9060:18

Limit 2 Counter Low

  Counter for "Limit 2 Low" events

UINT32

RO

0x00000000 (0dec)

9060:19

Limit 2 Counter High

  Counter for "Limit 2 High" events

UINT32

RO

0x00000000 (0dec)

9060:1A

Tare Value

 Tare value currently taken into account

REAL32

RO

0x00000000 (0.0)

9060:1B

Sampling rate

 Current effective sampling rate, [1/sec]

REAL32

RO

0x00000000 (0.0)

Index 9062 AI Output Current Info Data

Index (hex)

Name

Meaning

Data type

Flags

Default

9062:0

AI Output Current Info Data

Max. Subindex

UINT8

RO

0x12 (18dec)

9062:11

Vendor Calibration Counter

Counter for changes to the vendor adjustment data

UINT32

RO

0x00000000 (0dec)

9062:12

User Calibration Counter

Counter for changes to the user calibration data

UINT32

RO

0x00000000 (0dec)

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

General information for the Modular Device Profiles (MDP)

Organizational information on the profiles used in the device and listed in 0xF010

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index distance of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0007 (7dec)

Index F010 Module Profile List

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module Profile List

Maximum subindex

UINT8

RO

0x07 (7dec)

F010:01

Subindex 001

Profile 300

INT32

RO

0x00000190 (400dec)

F010:02

Subindex 002

Profile 300

INT32

RO

0x00000190 (400dec)

F010:03

Subindex 003

-

INT32

RO

0x00000000 (0dec)

F010:04

Subindex 004

Profile 300/-

INT32

RO

EL9501:
0x0000012C (300dec)

EL9561:
0x00000000 (0dec)

F010:05

Subindex 005

-

INT32

RO

0x00000000 (0dec)

F010:06

Subindex 006

Profile 300

INT32

RO

0x0000012C (300dec)

F010:07

Subindex 007

Profile 300

INT32

RO


0x0000012C (300dec)

Index F081 Download revision

Index (hex)

Name

Meaning

Data type

Flags

Default

F081:0

Download revision

Max. Subindex

UINT8

RO

0x01 (1dec)

F081:01

Download revision

The subindex 0xF081:01 (Download revision) describes the revision level of the module.

UINT32

RW

0x00000000 (0dec)

Index F900 DEV Info Data

Index (hex)

Name

Meaning

Data type

Flags

Default

F900:0

DEV Info Data

 Largest subindex of this object

UINT8

RO

0x14 (20dec)

F900:01

Power Good

see chapter "Device diagnostic functions"

BOOLEAN

RO

0x00 (0dec)

F900:11

Operating Time

UINT32

RO

0x00000000 (0dec)

F900:12

Device Temperature

REAL32

RO

0x00000000 (0.0)

F900:13

Min. Device Temperature

REAL32

RO

0x00000000 (0.0)

F900:14

Max. Device Temperature

REAL32

 

0x00000000 (0.0)

Index F915 LED Status

Index (hex)

Name

Meaning

Data type

Flags

Default

F915:0

LED Status

 Largest subindex of this object

UINT8

RO

0x06 (6dec)

F915:01

RUN

see chapter "Device diagnostic functions"

UINT32

RO

0x00000000 (0dec)

F915:02

Error

UINT32

RO

0x00000000 (0dec)

F915:05

Input OK

UINT32

RO

0x00000000 (0dec)

F915:06

Output

UINT32

RO

0x00000000 (0dec)

Index FB00 DEV Command

The command object is used for triggering an action in the terminal. The command is started by writing subindex 1 (request). Write access is disabled until the current command is completed.

Index (hex)

Name

Meaning

Data type

Flags

Default

FB00:0

PM Command

Largest subindex of this object

UINT8

RO

0x03 (3dec)

FB00:01

Request

Command value, for use see corresponding application chapter

OCTET-STRING [2]

RW

0x0000 (0dec)

FB00:02

Status

Command status, for use see corresponding application chapter

UINT8

RW

0x00 (0dec)

FB00:03

Response

Command response, for use see corresponding application chapter

OCTET-STRING [2]

RW

0x00000000 (0dec)