Configuration data

Index 8000 AO Output Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

AO Output Settings

Max. Subindex

UINT8

RO

0x16 (22dec)

8000:01

Enable User Scale

User scaling is enabled. (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8000:02

Presentation

0: “Signed presentation”
The measured value is displayed in two's complement.
Maximum presentation range at 16 bits:
-32768dec ... +32767dec

1: “Unsigned presentation”
Maximum presentation range for 16 bits:
0...+65535dec

2: “Absolute value with MSB as sign”
The measured value is output in the signed amount representation.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

3: “Absolute value”
The negative number range is also output as positive.

BIT3

RW

0x00 (0dec)

8000:05

Watchdog Type

0: “Default watchdog value”
The default value (0x8000:13) is active.

1: “Watchdog ramp”
The ramp (0x8000:14) for moving to the default value is active.

2: “Last output value”
The last process data is output when the watchdog drops.

BIT2

RW

0x00 (0dec)

8000:07

Enable user calibration

Enable user calibration (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8000:08

Enable Vendor Calibration

Enable vendor calibration (see “data stream flow chart”)

BOOLEAN

RW

0x01 (1dec)

8000:11

User Scale Offset

User scale offset

INT16

RW

0x0000 (0dec)

8000:12

User Scale Gain

User scale gain.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65535 (0x00010000).

INT32

RW

0x00010000 (65536dec)

8000:13

Watchdog Output Value

Watchdog default output value

INT16

RW

0x0000 (0dec)

8000:14

Watchdog Ramp

Ramps to the default value
Value in digits/ms.

UINT16

RW

0xFFFF (65535dec)

8000:15

User Calibration Offset

User calibration offset

INT16

RW

0x0000 (0dec)

8000:16

User Calibration Gain

User calibration gain

UINT16

RW

0x7FFF (32767dec)

Index 800C AO Output User Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

800C:0

AO Output User Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

800C:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

800C:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

800C:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

800C:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0)

800C:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

Index 800D AO Output Advanced Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

800D:0

AO Output Advanced Settings

Max. Subindex

UINT8

RO

0x29 (41dec)

800D:11

Output Interface

Values:

0 – “None”
13 – “V 0-20 V”
15 – “V 0-5 V”

UINT16

RW

0x000D (13dec)

800D:12

Integer Scaler

Values:

3 – “Legacy Range”

UINT16

RW

0x0003 (3dec)

800D:13

User Scale Offset (Real32)

User scale offset

REAL32

RW

0x00000000 (0.0)

800D:14

User Scale Gain (Real32)

User scale gain.

REAL32

RW

0x3F800000 (1.0)

800D:15

Warning Level Low

Warning if output value falls below permitted value

REAL32

RW

0x00000000 (-0.0)

800D:16

Warning Level High

Warning if permissible output value is exceeded

REAL32

RW

0x41A00000 (20.0)

800D:1A

Watchdog Output Value (Real32)

User-specific setpoint Watchdog (Real32)

REAL32

RW

0x00000000 (0.0)

800D:1B

Watchdog Ramp (Real32)

Time of the ramp from maximum value (20 V/5 V) to zero. The end value is defined via watchdog value 0x18 [s]

REAL32

RW

0x00000000 (0.0)

800D:1C

Limiter Low Value

Output value limit (lowest value)

REAL32

RW

0x00000000 (0.0)

800D:1D

Limiter High Value

Output value limit (highest value)

REAL32

RW

0x41A9999A (21.2)

800D:1E

Output Slew Rate

Limitation of the setpoint gradient [s]

REAL32

RW

0x3DCCCCCD (0.1)

800D:23

PowerOn Output Operation

Values:

0 – “Line off”
1 – “Line on”

UINT16

RW

0x0001 (1dec)

800D:24

PowerOn Output Value

Output value if PDO 0x1600, 0x1601, 0x1602 or 0x1603 is not active.

REAL32

RW

0x00000000 (0.0)

800D:26

Output Overload Acceptance Time

Time in seconds until an error message is issued in the event of an overload.

REAL32

RW

0x3D4CCCCD (0.005)

800D:29

Overcurrent Behavior

Values:

0 – “Switch off”
1 – “Current Limit”

UINT16

RW

0x0001 (1dec)

Index 800F AO Output Vendor Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

800F:0

AO Output Vendor Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

800F:01

Calibration Date

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

800F:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

800F:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

800F:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0)

800F:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

Index 8010 AO Complementary Limit High Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

AO Complementary Limit High Settings

Max. Subindex

UINT8

RO

0x08 (8dec)

8010:02

Presentation

0: “Signed presentation”
The measured value is displayed in two's complement.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

1: “Unsigned presentation”
Maximum presentation range for 16 bits:
0...+65535dec

2: “Absolute value with MSB as sign”
The measured value is output in the signed amount representation.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

3: “Absolute value”
The negative number range is also output as positive.

BIT3

RW

0x00 (0dec)

8010:07

Enable user calibration

Enable user calibration (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8010:08

Enable Vendor Calibration

Enable vendor calibration (see “data stream flow chart”)

BOOLEAN

RW

0x01 (1dec)

Index 801C AO Complementary Limit High User Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

801C:0

AO Complementary Limit High User Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

801C:01

Calibration Date

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

801C:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0dec)

801C:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0dec)

801C:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0dec)

801C:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0dec)

Index 801D AO Complementary Limit High Advanced Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

801D:0

AO Output Advanced Settings

Max. Subindex

UINT8

RO

0x24 (36dec)

801D:11

Output Interface

Values:

0 – “None”
33 – “I 0-2 A”

UINT16

RW

0x0021 (33dec)

801D:12

Integer Scaler

Values:

3 – “Legacy Range”

UINT16

RW

0x0003 (3dec)

801D:15

Warning Level Low

Warning if output value falls below permitted value

REAL32

RW

0x000000000 (0.0)

801D:16

Warning Level High

Warning if permissible output value is exceeded

REAL32

RW

0x40000000 (2.0)

801D:1C

Limiter Low Value

Output value limit (lowest value)

REAL32

RW

0xFF7FFFFD (-3.402823e38)

801D:1D

Limiter High Value

Output value limit (highest value)

REAL32

RW

0x7F7FFFFD (3.402823e38)

801D:24

PowerOn Output Value

Output value (current limitation) if PDO 0x1610 or 0x1612 is not active

REAL32

RW

0x40000000 (2.0)

Index 801F AO Complementary Limit High Vendor Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

801F:0

AO Complementary Limit High Vendor Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

801F:01

Calibration Date

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

801F:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0dec)

801F:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0dec)

801F:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0dec)

801F:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0dec))

Index 8030 AI Input Voltage Settings*)

Index (hex)

Name

Meaning

Data type

Flags

Default

8030:0

AI Input Voltage Settings

Max. Subindex

UINT8

RO

0x18 (24dec)

8030:01

Enable User Scale

User scaling is enabled. (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8030:02

Presentation

0: “Signed presentation”
The measured value is displayed in two's complement.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

1: Unsigned presentation
Maximum presentation range for 16 bits:
0...+65535dec

2: “Absolute value with MSB as sign”
The measured value is output in the signed amount representation.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

3: “Absolute value”
The negative number range is also output as positive.

BIT3

RW

0x00 (0dec)

8030:06

Enable Filter 1

Enable filter 1

BOOLEAN

RW

0x01 (1dec)

8030:07

Enable Limit 1

Enable Limit 1

BOOLEAN

RW

0x00 (0dec)

8030:08

Enable Limit 2

Enable Limit 2

BOOLEAN

RW

0x00 (0dec)

8030:0A

Enable User Calibration

Enable user calibration (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8030:0B

Enable Vendor Calibration

Enable vendor calibration (see “data stream flow chart”)

BOOLEAN

RW

0x01 (1dec)

8030:0E

Swap Limit Bits

Swap limit bits

BOOLEAN

RW

0x00 (0dec)

8030:11

User Scale Offset

User scale offset

INT16

RW

0x0000 (0dec)

8030:12

User Scale Gain

User scale gain.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65535 (0x00010000).

INT32

RW

0x00010000 (65536dec)

8030:13

Limit 1

First limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8030:14

Limit 2

Second limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8030:15

Filter 1 Settings

This object determines the digital filter settings if it is active via “Enable filter” (index 0x8000:06).
The possible settings are numbered consecutively.

0: 50 Hz FIR
1: 60 Hz FIR
2: IIR 1
3: IIR 2
4: IIR 3
5: IIR 4
6: IIR 5
7: IIR 6
8: IIR 7
9: IIR 8
Refer to the Note on setting the filter characteristics

UINT16

RW

0x0000 (0dec)

8030:17

User Calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

8030:18

User Calibration gain

User calibration gain

UINT16

RW

0x7FFF (32767dec)

*) only for EL9501

Index 803C AI Input Voltage User Calibration Data*)

Index (hex)

Name

Meaning

Data type

Flags

Default

80nC:0

AI Input Voltage User Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

80nC:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

80nC:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

80nC:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

80nC:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0)

80nC:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

*) only for EL9501

Index 803D AI Input Voltage Advanced Settings*)

Index (hex)

Name

Meaning

Data type

Flags

Default

803D:0

AI Input Voltage Advanced Settings

Max. Subindex

UINT8

RO

0x2A (42dec)

803D:11

Input Interface

Values:

0 – “None”
12 – “V 0-30 V”

UINT16

RW

0x000C (12dec)

803D:12

Integer Scaler

Values:

0 – “Extended Range”
3 – “Legacy Range”

UINT16

RW

0x0000 (0dec)

803D:17

Low Range Error

Low Range limit value

INT32

RW

0x00000000 (0dec)

803D:018

High Range Error

High Range limit value

INT32

RW

0x00007FFF (32767dec)

803D:1C

User Scale Offset (Real32)

User scale offset

REAL32

RW

0x00000000 (0.0)

803D:1D

User Scale Gain (Real32)

User scale gain.

REAL32

RW

0x3F800000 (1.0)

803D:27

Low Range Error (Real32)

Limit value Low Range (Real32)

REAL32

RW

0x00000000 (0.0)

803D:28

High Range Error (Real32)

High Range limit value (Real32)

REAL32

RW

0x4200D7E4 (32.21083)

803D:29

Limit 1 (Real32)

Limit value Limit1

REAL32

RW

0x00000000 (0.0)

803D:2A

Limit 2 (Real32)

Limit value Limit 2

REAL32

RW

0x00000000 (0.0)

*) only for EL9501

Index 803F AI Input Voltage Vendor Calibration Data*)

Index (hex)

Name

Meaning

Data type

Flags

Default

803F:0

AI Input Voltage Vendor Calibration Data

Max. Subindex

UINT8

RO

0x08 (8dec)

803F:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

803F:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

803F:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

803F:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0))

803F:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

803F:07

T1

Real32 coefficient T1

REAL32

RW

0x00000000 (0.0)

803F:08

T1S1

Real32 coefficient T1S1

REAL32

RW

0x00000000 (0.0)

*) only for EL9501

Index 8050 AI Output Voltage Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8050:0

AI Output Voltage Settings

Max. Subindex

UINT8

RO

0x18 (24dec)

8050:01

Enable User Scale

User scaling is enabled. (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8050:02

Presentation

0: “Signed presentation”
The measured value is displayed in two's complement.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

1: “Unsigned presentation”
Maximum presentation range for 16 bits:
0...+65535dec

2: “Absolute value with MSB as sign”
The measured value is output in the signed amount representation.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

3: “Absolute value”
The negative number range is also output as positive.

BIT3

RW

0x00 (0dec)

8050:06

Enable Filter 1

Enable filter 1

BOOLEAN

RW

0x01 (1dec)

8050:07

Enable Limit 1

Enable Limit 1

BOOLEAN

RW

0x00 (0dec)

8050:08

Enable Limit 2

Enable Limit 2

BOOLEAN

RW

0x00 (0dec)

8050:0A

Enable User Calibration

Enable user calibration (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8050:0B

Enable Vendor Calibration

Enable vendor calibration (see “data stream flow chart”)

BOOLEAN

RW

0x01 (1dec)

8050:0E

Swap Limit Bits

Swap limit bits

BOOLEAN

RW

0x00 (0dec)

8050:11

User Scale Offset

User scale offset

INT16

RW

0x0000 (0dec)

8050:12

User Scale Gain

User scale gain.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65535 (0x00010000).

INT32

RW

0x00010000 (65536dec)

8050:13

Limit 1

First limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8050:14

Limit 2

Second limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8050:15

Filter 1 Settings

This object determines the digital filter settings if it is active via “Enable filter” (index 0x8000:06).
The possible settings are numbered consecutively.

0: 50 Hz FIR
1: 60 Hz FIR
2: IIR 1
3: IIR 2
4: IIR 3
5: IIR 4
6: IIR 5
7: IIR 6
8: IIR 7
9: IIR 8
Refer to the Note on setting the filter characteristics

UINT16

RW

0x0000 (0dec)

8050:17

User Calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

8050:18

User Calibration gain

User calibration gain

UINT16

RW

0x7FFF (32767dec)

Index 805C AI Output Voltage User Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

800C:0

AI Output Voltage User Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

800C:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

800C:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

800C:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

800C:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0)

800C:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

Index 805D AI Output Voltage Advanced Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

805D:0

AI Output Voltage Advanced Settings

Max. Subindex

UINT8

RO

0x2A (42dec)

805D:11

Input Interface

Values:

0 – “None”
13 – “V 0-20 V”
15 – “V 0-5 V”

UINT16

RW

0x000C (13dec)

805D:12

Integer Scaler

Values:

0 – “Extended Range”
3 – “Legacy Range”

UINT16

RW

0x0000 (0dec)

805D:17

Low Range Error

Low Range limit value

INT32

RW

0x00000000 (0dec)

805D:018

High Range Error

High Range limit value

INT32

RW

0x00007FFF (32767dec)

805D:1C

User Scale Offset (Real32)

User scale offset

REAL32

RW

0x00000000 (0.0)

805D:1D

User Scale Gain (Real32)

User scale gain.

REAL32

RW

0x3F800000 (1.0)

805D:27

Low Range Error (Real32)

Limit value Low Range (Real32)

REAL32

RW

0x00000000 (0.0)

805D:28

High Range Error (Real32)

High Range limit value (Real32)

REAL32

RW

0x41ABCA82 (21.47388)

805D:29

Limit 1 (Real32)

Limit value Limit1

REAL32

RW

0x00000000 (0.0)

805D:2A

Limit 2 (Real32)

Limit value Limit 2

REAL32

RW

0x00000000 (0.0)

Index 805F AI Output Voltage Vendor Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

805F:0

AI Output Voltage Vendor Calibration Data

Max. Subindex

UINT8

RO

0x08 (8dec)

805F:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

805F:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

805F:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

805F:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0))

805F:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

805F:07

T1

Real32 coefficient T1

REAL32

RW

0x00000000 (0.0)

805F:08

T1S1

Real32 coefficient T1S1

REAL32

RW

0x00000000 (0.0)

Index 8060 AI Output Current Setting

Index (hex)

Name

Meaning

Data type

Flags

Default

8060:0

AI Output Current Setting

Max. Subindex

UINT8

RO

0x18 (24dec)

8060:01

Enable User Scale

User scaling is enabled. (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8060:02

Presentation

0: “Signed presentation”
The measured value is displayed in two's complement.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

1: “Unsigned presentation”
Maximum presentation range for 16 bits:
0...+65535dec

2: “Absolute value with MSB as sign”
The measured value is output in the signed amount representation.
Maximum presentation range at 16 bits:
-32768dec...+32767dec

3: “Absolute value”
The negative number range is also output as positive.

BIT3

RW

0x00 (0dec)

8060:06

Enable Filter 1

Enable filter 1

BOOLEAN

RW

0x01 (1dec)

8060:07

Enable Limit 1

Enable Limit 1

BOOLEAN

RW

0x00 (0dec)

8060:08

Enable Limit 2

Enable Limit 2

BOOLEAN

RW

0x00 (0dec)

8060:0A

Enable User Calibration

Enable user calibration (see “data stream flow chart”)

BOOLEAN

RW

0x00 (0dec)

8060:0B

Enable Vendor Calibration

Enable vendor calibration (see “data stream flow chart”)

BOOLEAN

RW

0x01 (1dec)

8060:0E

Swap Limit Bits

Swap limit bits

BOOLEAN

RW

0x00 (0dec)

8060:11

User Scale Offset

User scale offset

INT16

RW

0x0000 (0dec)

8060:12

User Scale Gain

User scale gain.
The gain has a fixed-point representation with a factor of 2-16.
The value 1 corresponds to 65535 (0x00010000).

INT32

RW

0x00010000 (65536dec)

8060:13

Limit 1

First limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8060:14

Limit 2

Second limit value for setting the status bits

INT16

RW

0x0000 (0dec)

8060:15

Filter 1 Settings

This object determines the digital filter settings if it is active via “Enable filter” (index 0x8000:06).
The possible settings are numbered consecutively.

0: 50 Hz FIR
1: 60 Hz FIR
2: IIR 1
3: IIR 2
4: IIR 3
5: IIR 4
6: IIR 5
7: IIR 6
8: IIR 7
9: IIR 8
Refer to the Note on setting the filter characteristics

UINT16

RW

0x0000 (0dec)

8060:17

User Calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

8060:18

User Calibration gain

User calibration gain

UINT16

RW

0x7FFF (32767dec)

Index 806C AI Output Current User Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

806C:0

AI Output Current User Calibration Data

Max. Subindex

UINT8

RO

0x06 (6dec)

806C:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

806C:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

806C:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

806C:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0)

806C:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

Index 806D AI Output Current Advanced Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

806D:0

AI Output Current Advanced Settings

Max. Subindex

UINT8

RO

0x2A (42dec)

806D:11

Input Interface

Values:

0 – “None”
33 – “I 0-2 A”
15 – “V 0-5 V”

UINT16

RW

0x0021 (33dec)

806D:12

Integer Scaler

Values:

0 – “Extended Range”
3 – “Legacy Range”

UINT16

RW

0x0000 (0dec)

806D:17

Low Range Error

Low Range limit value

INT32

RW

0x00000000 (0dec)

806D:018

High Range Error

High Range limit value

INT32

RW

0x00007FFF (32767dec)

806D:1C

User Scale Offset (Real32)

User scale offset

REAL32

RW

0x00000000 (0.0)

806D:1D

User Scale Gain (Real32)

User scale gain.

REAL32

RW

0x3F800000 (1.0)

806D:27

Low Range Error (Real32)

Limit value Low Range (Real32)

REAL32

RW

0x00000000 (0.0)

806D:28

High Range Error (Real32)

High Range limit value (Real32)

REAL32

RW

0x 40096EAD (2.14738)

806D:29

Limit 1 (Real32)

Limit value Limit1

REAL32

RW

0x00000000 (0.0)

806D:2A

Limit 2 (Real32)

Limit value Limit 2

REAL32

RW

0x00000000 (0.0)

Index 806F AI Output Current Vendor Calibration Data

Index (hex)

Name

Meaning

Data type

Flags

Default

806F:0

AI Output Voltage Vendor Calibration Data

Max. Subindex

UINT8

RO

0x08 (8dec)

806F:01

Calibration Data

4 bytes of free memory space;
here it is possible to store the calibration date in the form of 8 CHAR, for example

OCTET-STRING[4]

RW

{0}

806F:03

S0

Real32 coefficient S0

REAL32

RW

0x00000000 (0.0)

806F:04

S1

Real32 coefficient S1

REAL32

RW

0x00000000 (0.0)

806F:05

S2

Real32 coefficient S2

REAL32

RW

0x00000000 (0.0))

806F:06

S3

Real32 coefficient S3

REAL32

RW

0x00000000 (0.0)

806F:07

T1

Real32 coefficient T1

REAL32

RW

0x00000000 (0.0)

806F:08

T1S1

Real32 coefficient T1S1

REAL32

RW

0x00000000 (0.0)