UL notice
| ||
![]() | Application Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT System only. | |
| ||
![]() | Examination For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire and electrical shock (in accordance with UL508 and CSA C22.2 No. 142). | |
| ||
![]() | For devices with Ethernet connectors Not for connection to telecommunication circuits. | |
NOTICE | ||
![]() | Usage of suitable copper cables In order to comply with UL approval, use copper cables that are designed for operating temperatures >= 105°C. | |
Basic principles
UL certification according to UL508. Devices with this kind of certification are marked by this sign:


