Analog current/voltage input, AI_1xC, AI_1xV (0x382199, 0x302199)
Overview 0x1AA0 for analog input (SlotGroup 4)
Index (hex)  | Index name for ModuleGroups (ModuleIdent):  | |
|---|---|---|
AI_1xC (0x382199)  | AI_1xV (0x302199)  | |
1AA0:0  | AI_1xC TxPDO‑Map SlotGroup 4 (Slot 11) Inputs 1  | AI_1xV TxPDO‑Map SlotGroup 4 (Slot 11) Inputs 1  | 
Index 1AA0 AI_1xC/1xV TxPDO-Map SlotGroup 4 (Slot 11) Inputs 1
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1AA0:0  | AI_1xC/1xV TxPDO-Map SlotGroup 4  | PDO Mapping TxPDO 9  | UINT8  | RO  | 0x07 (7dec)  | 
1AA0:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x01 (Underrange))  | UINT32  | RO  | 0x60A0:01, 1  | 
1AA0:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x02 (Overrange))  | UINT32  | RO  | 0x60A0:02, 1  | 
1AA0:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x03 (Limit 1))  | UINT32  | RO  | 0x60A0:03, 2  | 
1AA0:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x05 (Limit 2))  | UINT32  | RO  | 0x60A0:05, 2  | 
1AA0:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x07 (Error))  | UINT32  | RO  | 0x60A0:07, 1  | 
1AA0:06  | SubIndex 006  | 6. PDO Mapping entry (9 bits align)  | UINT32  | RO  | 0x0000:00, 9  | 
1AA0:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x60A0 (SlotGroup 4 (Slot 11) AI Inputs 1), entry 0x11 (Value))  | UINT32  | RO  | 0x60A0:11, 1  |