Encoder with digital inputs/outputs, ENC (0x582199)
Overview 0x16n0 and 0x1An0 for encoders with digital inputs/outputs (SlotGroup 1)
Index (hex)  | Index name for ModuleGroups (ModuleIdent):  | ||
|---|---|---|---|
ENC_DI_DO  | ENC_2xDI  | ENC_2xDO  | |
1600:0  | ENC RxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 1  | ENC RxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 1  | ENC  | 
1610:0  | -  | -  | DOS RxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 1  | 
1620:0  | DOS RxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 1  | -  | DOS RxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 2  | 
1A00:0  | ENC TxPDO‑Map SlotGroup 1 (Slot 1, 2, 3, 4) Inputs 1  | ENC TxPDO‑Map SlotGroup 1  | ENC TxPDO‑Map SlotGroup 1  | 
1A10:0  | DIP TxPDO‑Map SlotGroup 1  | DIP TxPDO‑Map SlotGroup 1  | -  | 
1A20:0  | -  | DIP TxPDO‑Map SlotGroup 1  | -  | 
Index 1600 ENC RxPDO-Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs 1
Applies to ModuleGroup:  | 
ENC_DI_DO (0x582199, 0x82199, 0x402199)  | 
ENC_2xDI (0x582199, 0x82199, 0x82199)  | 
ENC_2xDO (0x582199, 0x402199, 0x402199)  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1600:0  | ENC  | PDO Mapping RxPDO 1  | UINT8  | RO  | 0x06 (6dec)  | 
1600:01  | SubIndex 001  | 1. PDO Mapping entry (2 bits align)  | UINT32  | RO  | 0x0000:00, 2  | 
1600:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x7000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Outputs status), entry 0x03 (Set counter))  | UINT32  | RO  | 0x7000:03, 1  | 
1600:03  | SubIndex 003  | 3. PDO Mapping entry (5 bits align)  | UINT32  | RO  | 0x0000:00, 5  | 
1600:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x7000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Outputs status), entry 0x09 (Set software gate))  | UINT32  | RO  | 0x7000:09, 1  | 
1600:05  | SubIndex 005  | 5. PDO Mapping entry (7 bits align)  | UINT32  | RO  | 0x0000:00, 7  | 
1600:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x7000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Outputs status, entry 0x11 (Set counter value))  | UINT32  | RO  | 0x7000:11, 32  | 
Index 16n0 DOS RxPDO-Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs %C
Applies to ModuleGroup:  | Values for n  | 
ENC_DI_DO (0x582199, 0x82199, 0x402199)  | n = 2 for DO 1  | 
ENC_2xDO (0x582199, 0x402199, 0x402199)  | n = 1 for DO 1, n = 2 for DO 2  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
16n0:0  | DOS RxPDO-Map SlotGroup 1 (Slot 1, 2, 3, 4) Outputs %C  | PDO Mapping RxPDO (n+1)  | UINT8  | RO  | 0x02 (2dec)  | 
16n0:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x70n0 (SlotGroup 1 (Slot 1, 2, 3, 4) DOS Outputs %C), entry 0x01 (Output))  | UINT32  | RO  | 0x70n0:01, 1  | 
16n0:02  | SubIndex 002  | 2. PDO Mapping entry (15 bits align)  | UINT32  | RO  | 0x0000:00, 15  | 
Index 1A00 ENC TxPDO-Map SlotGroup 1 (Slot 1, 2, 3, 4) Inputs 1
Applies to ModuleGroup:  | 
ENC_DI_DO (0x582199, 0x82199, 0x402199)  | 
ENC_2xDI (0x582199, 0x82199, 0x82199)  | 
ENC_2xDO (0x582199, 0x402199, 0x402199)  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A00:0  | ENC TxPDO-Map SlotGroup 1  | PDO Mapping TxPDO 1  | UINT8  | RO  | 0x0B (11dec)  | 
1A00:01  | SubIndex 001  | 1. PDO Mapping entry (2 bits align)  | UINT32  | RO  | 0x0000:00, 2  | 
1A00:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x03 (Set counter done))  | UINT32  | RO  | 0x6000:03, 1  | 
1A00:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x04 (Counter underflow))  | UINT32  | RO  | 0x6000:04, 1  | 
1A00:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x04 (Counter overflow))  | UINT32  | RO  | 0x6000:05, 1  | 
1A00:05  | SubIndex 005  | 5. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | 
1A00:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x09 (Status of input A))  | UINT32  | RO  | 0x6000:09, 1  | 
1A00:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x0A (Status of input B))  | UINT32  | RO  | 0x6000:0A, 1  | 
1A00:08  | SubIndex 008  | 8. PDO Mapping entry (6 bits align)  | UINT32  | RO  | 0x0000:00, 6  | 
1A00:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6002 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status 1), entry 0x11 (Software gate valid))  | UINT32  | RO  | 0x6002:11, 1  | 
1A00:0A  | SubIndex 010  | 10. PDO Mapping entry (15 bits align)  | UINT32  | RO  | 0x0000:00, 15  | 
1A00:0B  | SubIndex 011  | 11. PDO Mapping entry (object 0x6000 (SlotGroup 1 (Slot 1, 2, 3, 4) ENC Inputs status), entry 0x11 (Counter value))  | UINT32  | RO  | 0x6000:11, 32  | 
Index 1An0 DIP TxPDO-Map SlotGroup 1 (Slot 1, 2, 3, 4) Inputs %C
Applies to ModuleGroup:  | Values for n  | 
ENC_DI_DO (0x582199, 0x82199, 0x402199)  | n = 1 for DI 1  | 
ENC_2xDI (0x582199, 0x82199, 0x82199)  | n = 1 for DI 1, n = 2 for DI 2  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1An0:0  | DIP TxPDO-Map  | PDO Mapping TxPDO (n+1)  | UINT8  | RO  | 0x02 (2dec)  | 
1An0:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x60n0 (SlotGroup 1 (Slot 1, 2, 3, 4) DIP Inputs %C), entry 0x01 (Input))  | UINT32  | RO  | 0x60n0:01, 1  | 
1An0:02  | SubIndex 002  | 2. PDO Mapping entry (15 bits align)  | UINT32  | RO  | 0x0000:00, 15  |