Data stream (0x682199, 0x602199)

The following flow chart shows the data stream for the analog output (processing of the raw data, as well as checking and correcting the process data when the limit values are reached).

Data stream (0x682199, 0x602199) 1:
Data stream for the analog output

Designation

CoE - Index

CoE - Name

Factory setting (default)

Meaning

Output type, Scaler

0x80BD:01

Output type

I 0 … 20 mA (18)

Selection of output range

0x80BD:12

Scaler

Extended Range (0)

Select scaling type:
Nominal output range (Legacy range) or
Technical output range (Extended range)

Range Error

0x80BD:17

Low Range Error

-32768dec

Lower error threshold,
if the output value < the set value,
the error bit is set.

0x80BD:18

High Range Error

32768dec

Upper error threshold,
if the output value > the set value,
the error bit is set.

Presentation

0x80B0:02

Presentation

Signed (0)

Select data format

Watchdog

0x80B0:05

Watchdog

Default watchdog value (0)

Select behavior in case of a communication interruption

0x80B0:13

Default output

0

Select output value in watchdog case

0x80B0:14

Default output ramp

65535dec

Select velocity to reach the default output value

User scale

0x80B0:01

Enable user scale

FALSE

Enable user scale

0x80B0:11

Offset

0

User scale offset

0x80B0:12

Gain

65535 dec

User scale gain

User calibration

0x80B0:07

Enable user calibration

FALSE

Enable user calibration

0x80B0:15

User calibration offset

0

User calibration offset

0x80B0:16

User calibration gain

65535dec

User calibration gain

Vendor calibration

0x80B0:08

Enable vendor calibration

TRUE

Enable vendor calibration

0x80BF:01
0x80BF:02

Calibration offset
Calibration gain

Parameters for vendor calibration
The vendor reserves the right to perform the basic calibration. Therefore, the vendor calibration cannot be changed.

DAC raw value

0x80BE:01

DAC raw value

 

DAC raw value