UL notice - Compact Motion
| 
 | ||
|  | Application Beckhoff EtherCAT modules are intended for use with Beckhoff’s UL Listed EtherCAT System only. | |
| 
 | ||
|  | Examination For cULus examination, the Beckhoff I/O System has only been investigated for risk of fire and electrical shock (in accordance with UL508 and CSA C22.2 No. 142). | |
| 
 | ||
|  | For devices with Ethernet connectors Not for connection to telecommunication circuits. | |
| 
 | ||
|  | Notes on motion devices 
 | |
Basic principles
UL certification according to UL508. Devices with this kind of certification are marked by this sign:

