EL73x2 - Technical data
| Technical data | EL7332 | EL7342 | 
|---|---|---|
| Number of channels | 2 DC motors, | 2 DC motors, | 
| Rated load voltage | 24 VDC (-15%/+20%) | 8 … 48 VDC | 
| Load type | DC brush motors, inductive | |
| Output current | 2 x 1.0 A | 2 x 3.5 A | 
| Output current | 2 x 3.0 A | 2 x 6.5 A | 
| PWM clock frequency | 30 kHz with 180° phase shift each | |
| Duty factor | 0 … 100 % (voltage-controlled) | |
| Distributed Clocks | yes | |
| Control resolution | max. 10 bits current, 16 bits speed | |
| Supply voltage for electronic | via E-bus and power contacts | |
| Electrical isolation | 500 V (E-bus/field voltage) | |
| Current consumption via E-bus | typ. 140 mA | |
| Current consumption power contacts | typ. 40 mA + motor current | typ. 70 mA | 
| Current consumption sensor supply | - | typ. 20 mA | 
| Encoder/input signal | - | Signal voltage "0": | 
| - | Signal voltage "1": | |
| Nominal voltage of encoder signals | - | 5 ... 24 V, 5 mA, | 
| Signal voltage | 24 VDC | |
| Pulse frequency | - | 400,000 increments/s, | 
| Environmental conditions | EL7332 | EL7342 | 
|---|---|---|
| permissible ambient temperature range during operation | 0°C ... + 55°C | |
| permissible ambient temperature range during storage | -25°C ... + 85°C | |
| permissible relative humidity | 95 %, no condensation | |
| General data | EL7332 | EL7342 | 
|---|---|---|
| Weight | approx. 50 g | approx. 90 g | 
| Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm | approx. 27 mm x 100 mm x 70 mm | 
| on 35 mm mounting rail conforms to EN 60715 | ||
| Installation position | without fan cartridge ZB8610: standard installing position | |
| Standards and approvals | EL7332 | EL7342 | 
|---|---|---|
| Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27, | conforms to EN 60068-2-6 / EN 60068-2-27 | 
| EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |
| EMC category | Category C3 - standard | |
| Protection class | IP20 | |
| Approvals / markings* | CE, EAC, UKCA, | |
*) Real applicable approvals/markings see type plate on the side (product marking).