Number of outputs | 1 stepper motor, 2 phases | ||
Number of digital inputs | 2 limit position, 4 for an encoder system | 1 limit position, 4 for an encoder system | 2 limit position, 4 for an encoder system |
Number of digital outputs | - | 1 output, 24 VDC; 0.5 A | - |
Supply voltage | 8 VDC … 48 VDC | ||
Output current | 5 A (overload- and short-circuit-proof) | ||
Maximum step frequency | 1000, 2000, 4000, 8000, 16000, 32000 full steps/s (configurable) | ||
Step pattern | up to 64-fold micro stepping (automatic switching, speed-dependent) | ||
Current controller frequency | approx. 30 kHz | ||
Encoder pulse frequency | maximum 400,000 increments/s (4-fold evaluation) | ||
Input signal voltage "0" | -3 V … 2 V | ||
Input signal voltage "1" | 2.5 V … 28 V | ||
Input current | typ. 5 mA | ||
Diagnostic LED | Warning strand A and B, error strand A and B, power, enable | ||
Resolution | approx. 5,000 positions in typical applications (per revolution) | ||
Power supply | via the E-bus, encoder/driver stage: via the power contacts, motor: via terminal contacts | ||
Current consumption via E-bus | typ. 140 mA | ||
Electrical isolation | 500 V (E-bus/signal voltage) | ||
Configuration | no address setting required | ||
Supports NoCoeStorage function | from firmware 05 | from firmware 02 | |
Weight | approx. 105 g | ||
Permissible ambient temperature range during operation | 0°C ... + 55°C | ||
Permissible ambient temperature range during storage | -25°C ... + 85°C | ||
Permissible relative humidity | 95 %, no condensation | ||
Dimensions (W x H x D) | approx. 27 mm x 100 mm x 70 mm (width aligned: 24 mm) | ||
on 35 mm mounting rail conforms to EN 60715 | |||
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27, | conforms to EN 60068-2-6 / EN 60068-2-27 | |
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 | ||
EMC category | Category C3 - standard | ||
Protection class | IP20 | ||
Installation position | without fan cartridge ZB8610: standard installing position | ||
Approvals/markings* | CE, EAC, UKCA | CE, EAC, UKCA | CE, EAC, UKCA |