Selection of motor and feedback
- 1. In the Solution Explorer, expand the tree under the "Drive Manager 2 Project".
- 2. Double click on "Ch A".

- The Drive Manager 2 opens.
- 3. Select motor and feedback by clicking on the buttons "Select" in the corresponding lines "Motor" and "Feedback 1".

Feedback
When selecting the feedback, observe the following general conditions, especially the maximum input frequency:
Signal type | Max. input frequency 1) | Current sink 2.5 mA | Signal level | Signal level | Comment |
|---|---|---|---|---|---|
RS422 differential | 4 million inc/s | no | Udiff < -0.45 V | Udiff > +0.45 V | - |
TTL single ended | 250 kInc/s | yes | < 0.8 V | > 3.0 V | - |
TTL single ended – input filters disabled | 1 million inc/s | yes | < 0.8 V | > 3.0 V | Higher signal frequency possible. More sensitive to interference. |
Open collector | 125 kInc/s | no | < 0.8 V | > 2.0 V | Encoder switches to ground |
1) with 4-fold evaluation.