General technical data

E-bus

Electrical isolation

500 V (E-bus / I/O)

Distributed clocks

yes

Current consumption via E-bus

175 mA

Supply voltages

Electronics supply voltage

UP = 24 VDC via the power contacts

Current consumption from the power contacts

25 mA

+ brake output current

+ encoder supply 1)

1) The current consumption for the encoder supply is only approx. a quarter of the current consumption of the encoder because the encoder supply is regulated from 24 V to 5 V.

 

Environmental conditions

Ambient temperature during operation

0 … +55 °C

Ambient temperature during storage

-25 … +85 °C

Relative humidity

95 %, no condensation

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Approvals/markings

Approvals/markings

CE, cULus