General connection examples
| |
Risk of injury through electric shock and damage to the device! Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals. |
Notice | |
Connect the motor strands correctly! Connect the windings of a motor strand only to the terminal points of the same output driver of the stepper motor terminal, e.g.:
|
Connection types
The Stepper Motor terminal has bipolar output stages and can control bipolar and unipolar motors.
Notice | |
Fuse protection of the supply voltage The electrical protection of the load voltage must be selected in such a way that the maximum flowing current is limited to 3 times the rated current (max. 1 second)! |
Bipolar motors
Fig.29: Bipolar control (serial) of a bipolar motor
Fig.30: Bipolar control (parallel) of a bipolar motor![]() | Documentation for stepper motors from Beckhoff These two examples show the connection of the bipolar Beckhoff motors AS1010, AS1020, AS1030, AS1050 or AS1060. Further information on stepper motors from Beckhoff can be found in the associated documentation available for download from our website at http://www.beckhoff.com. |
Fig.31: Bipolar control of a unipolar motorOnly one half of each winding is controlled.